Table 19 — Fan Performance — 48/50P090 Units with Forward-Curved Fan
AIRFLOW
0.2
(cfm)
rpm
bhp
16,000
232
3.27
18,000
253
4.42
20,000
275
5.83
22,000
298
7.53
24,000
320
9.55
26,000
343
11.91
28,000
367
14.65
30,000
390
17.78
32,000
414
21.36
34,000
437
25.39
AIRFLOW
1.8
(cfm)
rpm
bhp
16,000
423
10.62
18,000
432
12.36
20,000
443
14.38
22,000
455
16.70
24,000
470
19.38
26,000
485
22.43
28,000
501
25.89
30,000
518
29.76
32,000
536
34.11
34,000
555
38.92
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
3.4
(cfm)
rpm
bhp
16,000
566
19.68
18,000
569
22.06
20,000
574
24.68
22,000
581
27.57
24,000
590
30.80
26,000
600
34.39
28,000
612
38.38
30,000
624
42.81
32,000
638
47.72
34,000
653
53.12
NOTE(S):
a. If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Component Pressure Drop table.
b. Fan performance is based on wet coils and clean 2 in. filters.
c. For return fan and high-capacity power exhaust units, add component pressure drop for economizer. Do not add component pressure drop for power exhaust.