Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 303

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

ITEM
CCN
CCN CONFIGURATION
CCNA
CCN Address
CCNB
CCN Bus Number
BAUD
CCN Baud Rate
BROD
CCN BROADCST DEFINITIONS
BRODTM.DT
CCN Time/Date Broadcast
BRODOAT.B
CCN OAT Broadcast
BRODORH.B
CCN OARH Broadcast
BRODOAQ.B
CCN OAQ Broadcast
BRODG.S.B
Global Schedule Broadcst
BRODB.ACK
CCN Broadcast Ack'er
SC.OV
CCN SCHEDULES-OVERRIDES
SC.OVSCH.N
Schedule Number
SC.OVHOL.T
Accept Global Holidays?
SC.OVO.T.L
Override Time Limit
SC.OVOV.EX
Timed Override Hours
SC.OVSPT.O
SPT Override Enabled?
SC.OVT58.O
T58 Override Enabled?
SC.OVGL.OV
Global Sched. Override?
ALLM
ALERT LIMIT CONFIG.
SP.L.O
SPT lo alert limit/occ
SP.H.O
SPT hi alert limit/occ
SP.L.U
SPT lo alert limit/unocc
SP.H.U
SPT hi alert limit/unocc
SA.L.O
EDT lo alert limit/occ
SA.H.O
EDT hi alert limit/occ
SA.L.U
EDT lo alert limit/unocc
SA.H.U
EDT hi alert limit/unocc
RA.L.O
RAT lo alert limit/occ
RA.H.O
RAT hi alert limit/occ
RA.L.U
RAT lo alert limit/unocc
RA.H.U
RAT hi alert limit/unocc
OAT.L
OAT lo alert limit
OAT.H
OAT hi alert limit
R.RH.L
RARH low alert limit
R.RH.H
RARH high alert limit
O.RH.L
OARH low alert limit
O.RH.H
OARH high alert limit
SP.L
SP low alert limit
SP.H
SP high alert limit
BP.L
BP lo alert limit
BP.H
BP high alert limit
IAQ.H
IAQ high alert limit
TRIM
SENSOR TRIM CONFIG.
SAT.T
Air Temp Lvg SF Trim
RAT.T
RAT Trim
OAT.T
OAT Trim
SPT.T
SPT Trim
L.SW.T
Limit Switch Trim
CCT.T
Air Temp Lvg Evap Trim
DTA.1
A1 Discharge Temp Trim
SP.A.T
Suct.Press.Circ.A Trim
SP.B.T
Suct.Press.Circ.B Trim
DP.A.T
Dis.Press.Circ.A Trim
DP.B.T
Dis.Press.Circ.B Trim
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
EXPANSION
RANGE
1 to 239
0 to 239
1 to 5 (multi-text strings)
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
0 to 99
YES/NO
0 to 4 HRS
0 to 4 HRS
YES/NO
YES/NO
YES/NO
–10 to 245 dF
–10 to 245 dF
–10 to 245 dF
–10 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
0 to 100%
0 to 100%
0 to 100%
0 to 100%
0 to 5 "H2O
0 to 5 "H2O
–0.25 to 0.25 "H2O
–0.25 to 0.25 "H2O
0 to 5000
–10 to 10 ^F
–10 to 10 ^F
–10 to 10 ^F
–10 to 10 ^F
–10 to 10 ^F
–10 to 10 ^F
–10 to 10 ^F
–50 to 50 PSIG
–50 to 50 PSIG
–50 to 50 PSIG
–50 to 50 PSIG
CL-25
DEFAULT
SETTING
1
0
3
On
Off
Off
Off
Off
Off
1
No
1
0
Yes
Yes
No
60
85
45
100
40
100
40
100
60
90
40
100
–40
150
0
100
0
100
0
2
–0.25
0.25
1200
0
0
0
0
0
0
0
0
0
0
0

Advertisement