ITEM
CCN
CCN CONFIGURATION
CCNA
CCN Address
CCNB
CCN Bus Number
BAUD
CCN Baud Rate
BROD
CCN BROADCST DEFINITIONS
BRODTM.DT
CCN Time/Date Broadcast
BRODOAT.B
CCN OAT Broadcast
BRODORH.B
CCN OARH Broadcast
BRODOAQ.B
CCN OAQ Broadcast
BRODG.S.B
Global Schedule Broadcst
BRODB.ACK
CCN Broadcast Ack'er
SC.OV
CCN SCHEDULES-OVERRIDES
SC.OVSCH.N
Schedule Number
SC.OVHOL.T
Accept Global Holidays?
SC.OVO.T.L
Override Time Limit
SC.OVOV.EX
Timed Override Hours
SC.OVSPT.O
SPT Override Enabled?
SC.OVT58.O
T58 Override Enabled?
SC.OVGL.OV
Global Sched. Override?
ALLM
ALERT LIMIT CONFIG.
SP.L.O
SPT lo alert limit/occ
SP.H.O
SPT hi alert limit/occ
SP.L.U
SPT lo alert limit/unocc
SP.H.U
SPT hi alert limit/unocc
SA.L.O
EDT lo alert limit/occ
SA.H.O
EDT hi alert limit/occ
SA.L.U
EDT lo alert limit/unocc
SA.H.U
EDT hi alert limit/unocc
RA.L.O
RAT lo alert limit/occ
RA.H.O
RAT hi alert limit/occ
RA.L.U
RAT lo alert limit/unocc
RA.H.U
RAT hi alert limit/unocc
OAT.L
OAT lo alert limit
OAT.H
OAT hi alert limit
R.RH.L
RARH low alert limit
R.RH.H
RARH high alert limit
O.RH.L
OARH low alert limit
O.RH.H
OARH high alert limit
SP.L
SP low alert limit
SP.H
SP high alert limit
BP.L
BP lo alert limit
BP.H
BP high alert limit
IAQ.H
IAQ high alert limit
TRIM
SENSOR TRIM CONFIG.
SAT.T
Air Temp Lvg SF Trim
RAT.T
RAT Trim
OAT.T
OAT Trim
SPT.T
SPT Trim
L.SW.T
Limit Switch Trim
CCT.T
Air Temp Lvg Evap Trim
DTA.1
A1 Discharge Temp Trim
SP.A.T
Suct.Press.Circ.A Trim
SP.B.T
Suct.Press.Circ.B Trim
DP.A.T
Dis.Press.Circ.A Trim
DP.B.T
Dis.Press.Circ.B Trim
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
EXPANSION
RANGE
1 to 239
0 to 239
1 to 5 (multi-text strings)
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
0 to 99
YES/NO
0 to 4 HRS
0 to 4 HRS
YES/NO
YES/NO
YES/NO
–10 to 245 dF
–10 to 245 dF
–10 to 245 dF
–10 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
–40 to 245 dF
0 to 100%
0 to 100%
0 to 100%
0 to 100%
0 to 5 "H2O
0 to 5 "H2O
–0.25 to 0.25 "H2O
–0.25 to 0.25 "H2O
0 to 5000
–10 to 10 ^F
–10 to 10 ^F
–10 to 10 ^F
–10 to 10 ^F
–10 to 10 ^F
–10 to 10 ^F
–10 to 10 ^F
–50 to 50 PSIG
–50 to 50 PSIG
–50 to 50 PSIG
–50 to 50 PSIG
CL-11
DEFAULT
SETTING
1
0
3
On
Off
Off
Off
Off
Off
1
No
1
0
Yes
Yes
No
60
85
45
100
40
100
40
100
60
90
40
100
–40
150
0
100
0
100
0
2
–0.25
0.25
1200
0
0
0
0
0
0
0
0
0
0
0