APPENDIX B — CCN TABLES (CONT)
Table P — MAINTENANCE DISPLAY TABLES (cont)
DISPLAY NAME
Economizer Installed?
Econ.Act.2 Installed?
Return Air Temperature
Air Temp Lvg Supply Fan
Outside Air Temperature
Occupied?
Supply Fan Relay
Supply Fan Commanded %
Economizer Act.Curr.Pos.
Economzr 2 Act.Curr.Pos.
Economizer Act.Cmd.Pos.
OK To Use Econ for T24?
OK Test Mech. D/C Act.
Title 24 Previous SAT
Title 24 Econ Samp Pos
Title 24 SAT Check Time
Elapsed Seconds
Title 24 Test Mark
RAT-OAT OK for Title 24
Title 24 Test Mark
SAT Moving Average
SAT Trend d/dt (F/min)
VFD1 Actual Motor Torque
T24 Auto-Test VFD Samp.
VFD1 Torque Moving Avg.
Economizer Act.Cmd.Pos.
Economizer Calibrate Cmd
Econ Act. Control Angle
Economzr 2 Act.Cmd.Pos.
Economzr 2 Calibrate Cmd
Econ2 Act. Control Angle
BP 1 Command Position
BP 1 Actuator Cal Cmd
BP Act.1 Control Angle
BP 1 Actuator Max Pos.
BP 2 Command Position
BP 2 Actuator Cal Cmd
BP Act.2 Control Angle
BP 2 Actuator Max Pos.
Ht.Coil Command Position
Heating Coil Act. Cal.Cmd
Heat Coil Act.Ctl.Angle
Humidifier Command Pos.
Humidifier Act. Cal.Cmd
Humidifier Act.Ctrl.Ang.
Econo Damper Command Pos
Static Pressure Setpoint
Requested Cool Stage
Compressor A1 Relay
Minimum Load Valve Relay
Compressor A1 Capacity
Two Circuit Start A1,B1
Compressor A2 Relay
Compressor A3 Relay
Compressor B1 Relay
Compressor B2 Relay
Compressor B3 Relay
Humidimizer 3-Way Valve
Condenser EXV Position
Bypass EXV Position
RANGE
UNITS
Yes/No
Yes/No
dF
dF
dF
Yes/No
On/Off
%
%
%
%
Yes/No
Yes/No
dF
%
Yes/No
dF
dF
%
dF
%
0 to 100
%
YES/NO
read only
0 to 100
%
YES/NO
read only
0 to 100
%
YES/NO
read only
0 to 100
%
0 to 100
%
YES/NO
read only
0 to 100
%
0 to 100
%
YES/NO
read only
0 to 100
%
YES/NO
read only
0 to 100
%
0 to 5
"H2O
0 to n
ON/OFF
ON/OFF
%
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
%
%
217
POINT NAME
WRITE STATUS
ECON_ENA
config
ECON_TWO
config
RAT
forcible
SAT
OAT
forcible
OCCUPIED
forcible
SFAN
SFAN_VFD
ECONOPOS
ECON2POS
ECONOCMD
forcible
T24ECOOL
OKTSTMDA
T24PRSAT
forcible
T24ECSMP
T24SATCT
ELAPSECS
T24TSMRK
T24RO_OK
T24TSMRK
SAT_MAVG
T24SATND
VFD1TORQ
T24VFDSM
VFD1TMAV
ECON1TST
ECONOCAL
ECONCANG
ECON2TST
ECON2CAL
ECN2CANG
BLDG1TST
BLDG1CAL
BP1_CANG
BP1SETMX
BLDG2TST
BLDG2CAL
BP2_CANG
BP2SETMX
HTCLACTC
HCOILCAL
HTCLCANG
HUMD_TST
HUMIDCAL
HUMDCANG
ECONCOOL
SPSP_TST
CLST_TST
CMPA1TST
MLV_TST
A1CAPTST
CMPABTST
CMPA2TST
CMPA3TST
CMPB1TST
CMPB2TST
CMPB3TST
RHVC_TST
CEXVCTST
BEXVCTST