ITEM
ECON
ECONOMIZER CONFIGURATION
EC.EN
Economizer Installed?
EC2.E
Econ.Act.2 Installed?
EC.MN
Economizer Min.Position
EC.MX
Economizer Max.Position
E.SEL
Econ ChangeOver Select
DDB.C
Diff Dry Bulb RAT Offset
E.TRM
Economzr Trim For SumZ?
OA.E.C
OA Enthalpy ChgOvr Selct
OA.EN
Outdr.Enth Compare Value
OAT.L
High OAT Lockout Temp
O.DEW
OA Dewpoint Temp Limit
ORH.S
Outside Air RH Sensor
CFM.C
OUTDOOR AIR CFM CONTROL
CFM.COCF.S
Outdoor Air CFM Sensor
CFM.CO.C.MX
Economizer Min.Flow
CFM.CO.C.MN
IAQ Demand Vent Min.Flow
CFM.CO.C.DB
Econ.Min.Flow Deadband
E.CFG
ECON.OPERATION CONFIGS
E.CFGE.P.GN
Economizer Prop.Gain
E.CFGE.RNG
Economizer Range Adjust
E.CFGE.SPD
Economizer Speed Adjust
E.CFGE.DBD
Economizer Deadband
UEFC
UNOCC.ECON.FREE COOLING
UEFCFC.CF
Unoc Econ Free Cool Cfg
UEFCFC.TM
Unoc Econ Free Cool Time
UEFCFC.L.O
Un.Ec.Free Cool OAT Lock
ACT.C
ECON.ACTUATOR CONFIGS
ACTCSN.1.1
Econ Serial Number 1
ACTCSN.1.2
Econ Serial Number 2
ACTCSN.1.3
Econ Serial Number 3
ACTCSN.1.4
Econ Serial Number 4
ACTCC.A.L1
Econ Ctrl Angle Lo Limit
ACTCSN.2.1
Econ 2 Serial Number 1
ACTCSN.2.2
Econ 2 Serial Number 2
ACTCSN.2.3
Econ 2 Serial Number 3
ACTCSN.2.4
Econ 2 Serial Number 4
ACTCC.A.L2
Econ 2 Ctrl Angle Lo Limit
T.24.C
TITLE 24 CONFIGS
T.24.CLOG.F
Log Title 24 Faults
T.24.CEC.MD
T24 Econ Move Detect
T.24.CEC.ST
T24 Econ Move SAT Test
T.24.CS.CHG
T24 Econ Move SAT Change
T.24.CE.SOD
T24 Econ RAT-OAT Diff
T.24.CE.CHD
T24 Heat/Cool End Delay
T.24.CSAT.T
SAT Settling Time
T.24.CET.MN
T24 Test Minimum Pos.
T.24.CET.MX
T24 Test Maximum Pos.
T.24.CAC.EC
Economizer Deadband Temp
T.24.CE.GAP
Econ Fault Detect Gap
T.24.CE.TMR
Econ Fault Detect Timer
T.24.CX.CFM
Excess Air CFM
T.24.CX.TMR
Excess Air Detect Timer
T.24.CAC.MR
T24 AutoTest SF Run Time
T.24.CAC.SP
T24 Auto-Test VFD Speed
T.24.CAC.OP
T24 Auto-Test Econ % Opn
T.24.CVF.PC
T24 Auto-Test VFD % Chng
T.24.CEC.DY
T24 Econ Auto-Test Day
T.24.CEC.TM
T24 Econ Auto-Test Time
EP.MS
ECON POS AT MIN VFD SPEED
EP.XS
ECON POS AT MAX VFD SPEED
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
EXPANSION
RANGE
Yes/No
Yes/No
0 to 100%
0 to 100%
0 to 3 (multi-text strings)
0 to 3
Yes/No
1 to 5 (multi-text strings)
18 to 28
–40 to 120 dF
50 to 62 dF
Enable/Disable
Enable/Disable
0 to 20000 CFM
0 to 20000 CFM
200 to 1000 CFM
0.7 to 3.0
0.5 to 5 ^F
0.1 to 10
0.1 to 2 ^F
0 to 2 (multi-text strings)
0 to 720 min
40 to 70 dF
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
Yes/No
1 to 10
10 to 20
0 to 5
5 to 20
0 to 60
10 to 900
0 to 50
50 to 100
0 to 10
2 to 100
10 to 240
400 to 4000
30 to 240
1 to 10
10 to 50
1 to 100
1 to 20
0=Never, 
1=Monday, 
2=Tuesday,
3=Wednesday, 
4=Thursday, 
5=Friday, 
6=Saturday, 
7=Sunday
0 to 23
CL-22
DEFAULT
SETTING
Yes
No
5
98
0
0
Yes
4
24
60
55
Disable
Disable
2000
0
400
1
2.5
0.75
0.5
0
120
50
0
0
0
0
85
0
0
0
0
85
No
1
10
0.2
15
25
240
15
85
4
5
20
800
150
2
20
50
10
6=Saturday
2