ITEM
ECON
ECONOMIZER CONFIGURATION
EC.EN
Economizer Installed?
EC2.E
Econ.Act.2 Installed?
EC.MN
Economizer Min.Position
EC.MX
Economizer Max.Position
E.SEL
Econ ChangeOver Select
DDB.C
Diff Dry Bulb RAT Offset
E.TRM
Economzr Trim For SumZ?
OA.E.C
OA Enthalpy ChgOvr Selct
OA.EN
Outdr.Enth Compare Value
OAT.L
High OAT Lockout Temp
O.DEW
OA Dewpoint Temp Limit
ORH.S
Outside Air RH Sensor
CFM.C
OUTDOOR AIR CFM CONTROL
CFM.COCF.S
Outdoor Air CFM Sensor
CFM.CO.C.MX
Economizer Min.Flow
CFM.CO.C.MN
IAQ Demand Vent Min.Flow
CFM.CO.C.DB
Econ.Min.Flow Deadband
E.CFG
ECON.OPERATION CONFIGS
E.CFGE.P.GN
Economizer Prop.Gain
E.CFGE.RNG
Economizer Range Adjust
E.CFGE.SPD
Economizer Speed Adjust
E.CFGE.DBD
Economizer Deadband
UEFC
UNOCC.ECON.FREE COOLING
UEFCFC.CF
Unoc Econ Free Cool Cfg
UEFCFC.TM
Unoc Econ Free Cool Time
UEFCFC.L.O
Un.Ec.Free Cool OAT Lock
ACT.C
ECON.ACTUATOR CONFIGS
ACTCSN.1.1
Econ Serial Number 1
ACTCSN.1.2
Econ Serial Number 2
ACTCSN.1.3
Econ Serial Number 3
ACTCSN.1.4
Econ Serial Number 4
ACTCC.A.L1
Econ Ctrl Angle Lo Limit
ACTCSN.2.1
Econ 2 Serial Number 1
ACTCSN.2.2
Econ 2 Serial Number 2
ACTCSN.2.3
Econ 2 Serial Number 3
ACTCSN.2.4
Econ 2 Serial Number 4
ACTCC.A.L2
Econ 2 Ctrl Angle Lo Limit
T.24.C
TITLE 24 CONFIGS
T.24.CLOG.F
Log Title 24 Faults
T.24.CEC.MD
T24 Econ Move Detect
T.24.CEC.ST
T24 Econ Move SAT Test
T.24.CS.CHG
T24 Econ Move SAT Change
T.24.CE.SOD
T24 Econ RAT-OAT Diff
T.24.CE.CHD
T24 Heat/Cool End Delay
T.24.CSAT.T
SAT Settling Time
T.24.CET.MN
T24 Test Minimum Pos.
T.24.CET.MX
T24 Test Maximum Pos.
T.24.CAC.EC
Economizer Deadband Temp
T.24.CE.GAP
Econ Fault Detect Gap
T.24.CE.TMR
Econ Fault Detect Timer
T.24.CX.CFM
Excess Air CFM
T.24.CX.TMR
Excess Air Detect Timer
T.24.CAC.MR
T24 AutoTest SF Run Time
T.24.CAC.SP
T24 Auto-Test VFD Speed
T.24.CAC.OP
T24 Auto-Test Econ % Opn
T.24.CVF.PC
T24 Auto-Test VFD % Chng
T.24.CEC.DY
T24 Econ Auto-Test Day
T.24.CEC.TM
T24 Econ Auto-Test Time
EP.MS
ECON POS AT MIN VFD SPEED
EP.XS
ECON POS AT MAX VFD SPEED
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
EXPANSION
RANGE
Yes/No
Yes/No
0 to 100%
0 to 100%
0 to 3 (multi-text strings)
0 to 3
Yes/No
1 to 5 (multi-text strings)
18 to 28
–40 to 120 dF
50 to 62 dF
Enable/Disable
Enable/Disable
0 to 20000 CFM
0 to 20000 CFM
200 to 1000 CFM
0.7 to 3.0
0.5 to 5 ^F
0.1 to 10
0.1 to 2 ^F
0 to 2 (multi-text strings)
0 to 720 min
40 to 70 dF
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
Yes/No
1 to 10
10 to 20
0 to 5
5 to 20
0 to 60
10 to 900
0 to 50
50 to 100
0 to 10
2 to 100
10 to 240
400 to 4000
30 to 240
1 to 10
10 to 50
1 to 100
1 to 20
0=Never,
1=Monday,
2=Tuesday,
3=Wednesday,
4=Thursday,
5=Friday,
6=Saturday,
7=Sunday
0 to 23
CL-22
DEFAULT
SETTING
Yes
No
5
98
0
0
Yes
4
24
60
55
Disable
Disable
2000
0
400
1
2.5
0.75
0.5
0
120
50
0
0
0
0
85
0
0
0
0
85
No
1
10
0.2
15
25
240
15
85
4
5
20
800
150
2
20
50
10
6=Saturday
2