Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 223

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

PARAMETER GROUP
Actual Signals
Not Available
Operating Data
Fault History
PARAMETER GROUP
Actual Signals
Not Available
Operating Data
VFD Operation
The VFD keypad is shown in Fig. B. The function of SOFT
KEYS 1 and 2 change depending on what is displayed on the
screen. The function of SOFT KEY 1 matches the word in the
lower left-hand box on the display screen. The function of SOFT
KEY 2 matches the word in the lower right-hand box on the dis-
play screen. If the box is empty, then the SOFT KEY does not
have a function on that specific screen. The UP and DOWN keys
are used to navigate through the menus. The OFF key is used to
turn off the VFD. The AUTO key is used to change control of the
drive to automatic control. The HAND key is used to change con-
trol of the drive to local (hand held) control. The HELP button is
used to access the help screens.
APPENDIX D — VFD INFORMATION (CONT)
Table AE — VFD ComfortLink Control Variables
PARAMETER TITLE
FB STS WORD 1
SPEED (%)
SPEED
OUTPUT FREQ
CURRENT
TORQUE
POWER
DC BUS VOLTAGE
OUTPUT VOLTAGE
DRIVE TEMP
RUN TIME (R)
KWH COUNTER (R)
DI1 STATUS
DI2 STATUS
DI3 STATUS
DI4 STATUS
DI5 STATUS
DI6 STATUS
AI1
AI2
LAST FAULT
Table AF — VFD ComfortLink Command Variables
PARAMETER TITLE
FB CMD WORD 1
SPEED REF (%)
COMM RO WORD - (RELAY
OUTPUT 1)
COMM RO WORD - (RELAY
OUTPUT 2)
COMM RO WORD - (RELAY
OUTPUT 3)
COMM VALUE 1 - (AO1)
COMM VALUE 2 - (AO2)
PARAMETER INDEX
SUPPLY FAN VFD
303
Not Available
102
103
104
105
106
107
109
110
114
115
118
118
118
119
119
119
120
121
401
PARAMETER INDEX
SUPPLY FAN VFD
301
Not Available
134
134
134
135
136
223
CCN POINT
CCN POINT
EXHAUST FAN VFD
VFD1STAT
VFD2STAT
VFD1_SPD
VFD2_SPD
VFD1rpm
VFD1FREQ
VFD2FREQ
VFD1AMPS
VFD2AMPS
VFD1TORQ
VFD2TORQ
VFD1PWR
VFD1VDC
VFD1VOUT
VFD2VOUT
VFD1TEMP
VFD2TEMP
VFD1RUNT
VFD2RUNT
VFD1KWH
VFD1_DI1
VFD1_DI2
VFD1_DI3
VFD1_DI4
VFD1_DI5
VFD1_DI6
VFD1_AI1
VFD1_A12
VFD1LFC
CCN POINT
CCN POINT
EXHAUST FAN VFD
Not Available
Not Available
SFAN_VFD
EFAN_VFD
VFD1REL1
VFD2REL1
VFD1REL2
VFD2REL2
VFD1REL3
VFD2REL3
VFD1_AO1
VFD2_AO1
VFD1_AO2
VFD2_AO2
Fig. B — VFD Keypad
VFD2rpm
VFD2PWR
VFD2VDC
VFD2KWH
VFD2_DI1
VFD2_DI2
VFD2_DI3
VFD2_DI4
VFD2_DI5
VFD2_DI6
VFD2_AI1
VFD2_A12
VFD2LFC