Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 284

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

MODEL NUMBER:
SERIAL NUMBER:
DATE:
TECHNICIAN:
ITEM
UNIT
C.TYP
SIZE
FN.MD
RM.CF
CEM
TCS.C
TCS.H
SFS.S
SFS.M
VAV.S
50.HZ
MAT.S
MAT.R
MAT.D
ALTI
DLAY
AUX.R
D.183
SV.DH
SENS
SENSSPT.S
SENSSP.O.S
SENSSP.O.R
SENSSRH.S
SENSRRH.S
SENSFLT.S
COOL
A1.EN
A2.EN
A3.EN
B1.EN
B2.EN
B3.EN
CS.A1
CS.A2
CS.A3
CS.B1
CS.B2
CS.B3
Z.GN
MC.LO
LLAG
M.M.
SCT.H
SCT.L
DG.A1
MC.A1
CONTROLS SET POINT AND
CONFIGURATION LOG (COOLING)
Software Version
MBB
RXB
EXB
NAVI
SCB
CEM
MARQ
CXB
EXV
EXPANSION
UNIT CONFIGURATION
Machine Control Type
Unit Size (30-100)
Fan Mode (0=Auto, 1=Cont)
Remote Switch Config
CEM Module Installed
Temp.Cmp.Strt.Cool Factr
Temp.Cmp.Strt.Heat Factr
Fan Fail Shuts Down Unit
Fan Stat Monitoring Type
VAV Unocc.Fan Retry Time
50 Hertz Unit?
MAT Calc Config
Reset MAT Table Entries?
MAT Outside Air Default
Altitude........in feet:
Startup Delay Time
Auxiliary Relay Config
Disable T183 Alert
SAV Optimized for Dehumidification
INPUT SENSOR CONFIG
Space Temp Sensor
Space Temp Offset Sensor
Space Temp Offset Range
Space Air RH Sensor
Return Air RH Sensor
Filter Stat.Sw.Enabled?
COOLING CONFIGURATION
Enable Compressor A1
Enable Compressor A2
Enable Compressor A3
Enable Compressor B1
Enable Compressor B2
Enable Compressor B3
CSB A1 Feedback Alarm
CSB A2 Feedback Alarm
CSB A3 Feedback Alarm
CSB B1 Feedback Alarm
CSB B2 Feedback Alarm
CSB B3 Feedback Alarm
Capacity Threshold Adjst
Compressor Lockout Temp
Lead/Lag Configuration
Motor Master Control?
Maximum Condenser Temp
Minimum Condenser Temp
A1 is a Digital Scroll
A1 Min Digital Capacity
CL-6
CESR131461--
CESR131465--
CESR131465--
CESR130227--
CESR131226--
CESR131174--
CESR131171--
CESR131173--
CESR131172--
RANGE
1 to 4 (multi-text strings)
3 to 100
1 to 1 (multi-text strings)
0 to 3 (multi-text strings)
Yes/No
0 to 60 min
0 to 60 min
Yes/No
0 to 2 (multi-text strings)
0 to 720 min
Yes/No
0 to 2 (multi-text strings)
Yes/No
0 to 100%
0 to 60000
0 to 900 secs
0 to 3 (multi-text strings)
0 to 1
Yes/No
Enable/Disable
Enable/Disable
1 to 10
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
0.1 to 10
–20 to 55 dF
0 to 2 (multi-text strings)
Yes/No
100 to 150 dF
40 to 90 dF
Yes/No
10 to 100%
DEFAULT
SETTING
4
30
1
0
No
0
0
No
0
50
No
1
No
20
0
0
0
Disable
Disable
5
Disable
Disable
Disable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable
1
53
0
No
115
72
No
50

Advertisement

Table of Contents
loading

This manual is also suitable for:

Weathermaster 50p030-100

Table of Contents