Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 205

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

TABLE
BP__
Building Press. Config
Building Pressure Sensor
Bldg. Press. (+/-) Range
Building Pressure Setp.
BP Setpoint Offset
Power Exhaust On Setp.1
Power Exhaust On Setp.2
VFD/Act. Fire Speed/Pos.
VFD/Act. Min. Speed/Pos.
VFD Maximum Speed
BP 1 Actuator Max Pos.
BP 2 Actuator Max Pos.
BP Hi Cap VFD Clamp Val.
Fan Track Learn Enable
Fan Track Learn Rate
Fan Track Initial DCFM
Fan Track Max Clamp
Fan Track Max Correction
Fan Track Internl EEPROM
Fan Track Internal RAM
Fan Track Reset Internal
Supply Air CFM Config
Bldg.Pres.PID Run Rate
Bldg.Press. Prop. Gain
Bldg.Press. Integ. Gain
Bldg.Press. Deriv. Gain
Prognostics BP Enable
Prognostics BP Deadband
BP 1 Serial Number 1
BP 1 Serial Number 2
BP 1 Serial Number 3
BP 1 Serial Number 4
BP1 Cntrl Angle Lo Limit
BP 2 Serial Number 1
BP 2 Serial Number 2
BP 2 Serial Number 3
BP 2 Serial Number 4
BP2 Cntrl Angle Lo Limit
COOL
Enable Compressor A1
Enable Compressor A2
Enable Compressor A3
Enable Compressor B1
Enable Compressor B2
Enable Compressor B3
CSB A1 Feedback Alarm
CSB A2 Feedback Alarm
CSB A3 Feedback Alarm
CSB B1 Feedback Alarm
CSB B2 Feedback Alarm
CSB B3 Feedback Alarm
Capacity Threshold Adjst
Compressor Lockout Temp
Lead/Lag Configuration
Motor Master Control?
Maximum Condenser Temp
Minimum Condenser Temp
A1 is a Digital Scroll
A1 Min Digital Capacity
Dig Scroll Adjust Delta
Dig Scroll Adjust Delay
Dig Scroll Reduce Delta
Dig Scroll Reduce Delay
Dig Scroll Reduction OAT
Dig Scroll Max Only OAT
Min Load Valve Enable
Hi SST Alert Delay Time
Rev Rotation Verified?
Use CSBs for HPS Detect
APPENDIX B — CCN TABLES (CONT)
Table O — SERVICE-CONFIG TABLES (cont)
DISPLAY NAME
RANGE
UNITS
0 to 5
Enable/Disable
0.10 to 0.25
"H2O
–0.25 to 0.25
"H2O
0 to 0.5
^"H2O
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
85 to 100
%
85 to 100
%
5 to 25
%
Yes/No
5-60
min
–20000 to 20000
CFM
0 to 20000
CFM
0 -20000
CFM
–20000 to 20000
CFM
–20000 to 20000
CFM
Yes/No
1 to 2 (multi-text strings)
5 to 120
sec
0 to 5
0 to 2
0 to 5
Disable/Enable
"H2O
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
–10 to 10
–25 to 55
dF
Yes/No
dF
dF
Yes/No
%
%
sec
%
sec
dF
dF
Enable/Disable
5 to 30
min
Yes/No
Yes/No
205
POINT NAME
DEFAULT
BLDG_CFG
0
BPSENS
Disable
BP_RANGE
0.25
BPSP
0.05
BPSO
0.05
PES1
25
PES2
75
BLDGPFSO
100
BLDGPMIN
10
BLDGPMAX
100
BP1SETMX
100
BP2SETMX
100
BLDGCLMP
10
DCFM_CFG
NO
DCFMRATE
15
DCFMSTRT
2000
DCFM_MAX
4000
DCFM_ADJ
1000
DCFM_OFF
0
DCFM_RAM
0
DCFMRSET
No
SCFM_CFG
1
BPIDRATE
10
BLDGP_PG
1
BLDGP_IG
1
BLDGP_DG
0.5
PG_BP_EN
PG_BP_DB
BP_1_SN1
0
BP_1_SN2
0
BP_1_SN3
0
BP_1_SN4
0
BP1_CALM
35
BP_2_SN1
0
BP_2_SN2
0
BP_2_SN3
0
BP_2_SN4
0
BP2_CALM
35
CMPA1ENA
Enable
CMPA2ENA
Enable
CMPA3ENA
Enable
CMPB1ENA
Enable
CMPB2ENA
Enable
CMPB3ENA
Enable
CSB_A1EN
Enable
CSB_A2EN
Enable
CSB_A3EN
Enable
CSB_B1EN
Enable
CSB_B2EN
Enable
CSB_B3EN
Enable
Z_GAIN
1
OATLCOMP
53
LEAD_LAG
MOTRMAST
No
SCT_MAX
SCT_MIN
DIGCMPA1
MINCAPA1
DSADJPCT
DSADJDLY
DSREDPCT
DSREDDLY
DSREDOAT
DSMAXOAT
MLV_ENAB
HSSTTIME
10
REVR_VER
CSbhpDET