Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 190

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

ITEM
GEN.I
GENERAL INPUTS
FLT.S
Filter Status Input
G.FAN
Fan Request From IGC
REMT
Remote Input State
ENTH
Enth. Switch Read High?
S.FN.S
Supply Fan Status Switch
FRZ.S
Freeze Status Switch
PP.SW
Plenum Press.Safety Sw.
DL.S1
Demand Limit Switch 1
DL.S2
Demand Limit Switch 2
DH.IN
Dehumidify Switch Input
FD.BK
COMPRESSOR FEEDBACK
HPS.A
Circ A High Press. Switch
HPS.B
Circ B High Press. Switch
CS.A1
Compressor A1 Feedback
CS.A2
Compressor A2 Feedback
CS.A3
Compressor A3 Feedback
CS.B1
Compressor B1 Feedback
CS.B2
Compressor B2 Feedback
CS.B3
Compressor B3 Feedback
STAT
THERMOSTAT INPUTS
G
Thermostat G Input
W1
Thermostat W1 Input
W2
Thermostat W2 Input
Y1
Thermostat Y1 Input
Y2
Thermostat Y2 Input
FIRE
FIRE-SMOKE INPUTS
FSD
Fire Shutdown Input
PRES
Pressurization Input
EVAC
Evacuation Input
PURG
Smoke Purge Input
REL.H
RELATIVE HUMIDITY
OA.RH
Outside Air Rel. Humidity
OA.EN
Outdoor Air Enthalpy
OA.DP
Outside Air Dewpoint Temp
RA.RH
Return Air Rel. Humidity
RA.EN
Return Air Enthalpy
SP.RH
Space Relative Humidity
SP.EN
Space Enthalpy
AIR.Q
AIR QUALITY SENSORS
IAQ.I
IAQ - Discrete Input
IAQ
IAQ - PPM Return CO2
OAQ
OAQ - PPM Return CO2
DAQ
Diff.Air Quality in PPM
IQ.P.O
IAQ Min.Pos. Override
CFM
CFM SENSORS
O.CFM
Outside Air CFM
R.CFM
Return Air CFM
S.CFM
Supply Air CFM
D.CFM
Fan Track Control D.CFM
RSET
RESET INPUTS
SA.S.R
Supply Air Setpnt. Reset
SP.RS
Static Pressure Reset
4-20
4-20 MILLIAMP INPUTS
IAQ.M
IAQ Milliamps
OAQ.M
OAQ Milliamps
SP.R.M
SP Reset milliamps
DML.M
4-20 ma Demand Signal
EDR.M
EDT Reset Milliamps
ORH.M
OARH Milliamps
SRH.M
SPRH Milliamps
RRH.M
RARH Milliamps
SAC.M
SACFM Milliamps
SA.M.T
Supply Air CFM Trim (ma)
RAC.M
RACFM Milliamps
RA.M.T
Return Air CFM Trim (ma)
OAC.M
OACFM Milliamps
OA.M.T
Outside Air CFM Trim(ma)
BP.M
BP Milliamps
BP.M.T
Bldg. Pressure Trim (ma)
SP.M
SP Milliamps
SP.M.T
Static Press. Trim (ma)
NOTE(S):
a. The display text changes depending on the remote switch configuration (Configuration
will be "On" or "Off." If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be "Occupied" or "Unoccupied." If RM.CF is set to 2 (Start/Stop), then
the display text will be "Stop" or "Start." If RM.CF is set to 3 (Override Switch), then the display text will be "No Override" or "Override."
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
Table F — MODE — INPUTS
EXPANSION
DRTY/CLN
ON/OFF
a
YES/NO
ON/OFF
ALRM/NORM
HIGH/LOW
ON/OFF
ON/OFF
ON/OFF
HIGH/LOW
HIGH/LOW
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ALRM/NORM
ALRM/NORM
ALRM/NORM
ALRM/NORM
HIGH/LOW
–2.0 to 2.0
–2.0 to 2.0
–2.0 to 2.0
–2.0 to 2.0
–2.0 to 2.0
RANGE
UNITS
FLTS
IGCFAN
RMTIN
ENTH
SFS
FRZ
PPS
DMD_SW1
DMD_SW2
DHDISCIN
CIRCAHPS
CIRCBHPS
CSB_A1
CSB_A2
CSB_A3
CSB_B1
CSB_B2
CSB_B3
G
W1
W2
Y1
Y2
FSD
PRES
EVAC
PURG
%
OARH
OAE
dF
OADEWTMP
%
RARH
RAE
%
SPRH
SPE
IAQIN
IAQ
OAQ
DAQ
%
IAQMINOV
CFM
OACFM
CFM
RACFM
CFM
SACFM
CFM
DELTACFM
^F
SASPRSET
SPRESET
ma
IAQ_MA
ma
OAQ_MA
ma
SPRST_MA
ma
DMDLMTMA
ma
EDTRESMA
ma
OARH_MA
ma
SPRH_MA
ma
RARH_MA
ma
SACFM_MA
SAMATRIM
ma
RACFM_MA
RAMATRIM
ma
OACFM_MA
OAMATRIM
ma
BP_MA
BPMATRIM
ma
SP_MA
SPMATRIM
UNIT
RM.CF). If RM.CF is set to 0 (No Remote Switch), then the display text
190
CCN POINT
WRITE STATUS
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
config
config
config
config