DOWNLOAD ALL PARAMETERS

To download all parameters from the control panel to the VFD,
perform the following procedure:
1. Install the control panel with the correct parameters onto
the replacement VFD.
2. Select MENU (SOFT KEY 2). The Main menu will be
displayed.
3. Use the UP or DOWN keys to highlight PAR BACKUP
on the display screen and press ENTER (SOFT KEY 2).
4. Use the UP or DOWN keys to highlight DOWNLOAD
TO DRIVE ALL and press SEL (SOFT KEY 2).
5. The text "Restoring Parameters" will be displayed with a
progress indicator. To stop the process, select ABORT
(SOFT KEY 1).
6. When the download is complete, the text "Parameter
download successful" will be displayed.
7. The display will then return to the PAR BACKUP menu.
Select EXIT (SOFT KEY 1) to return to the main menu.
8. The control panel can now be disconnected from the
drive.

CLOCK SET MODE

The Clock Set mode is used for setting the date and time for the in-
ternal clock of the VFD. In order to use the timer functions of the
VFD control, the internal clock must be set. The date is used to de-
termine weekdays and is visible in the fault logs.
To set the clock, perform the following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will be
displayed.
2. Use the UP or DOWN keys to highlight CLOCK SET on
the display screen and press ENTER (SOFT KEY 2). The
clock set parameter list will be displayed.
3. Use the UP or DOWN keys to highlight CLOCK VISI-
BILITY and press SEL (SOFT KEY 2). This parameter is
used to display or hide the clock on the screen. Use the
UP or DOWN keys to change the parameter setting. Press
OK (SOFT KEY 2) to save the configuration and return
to the Clock Set menu.
4. Use the UP or DOWN keys to highlight SET TIME and
press SEL (SOFT KEY 2). Use the UP or DOWN keys to
change the hours and minutes. Press OK (SOFT KEY 2)
to save the configuration and return to the Clock Set
menu.
5. Use the UP or DOWN keys to highlight TIME FORMAT
and press SEL (SOFT KEY 2). Use the UP and DOWN
keys to change the parameter setting. Press OK (SOFT
KEY 2) to save the configuration and return to the Clock
Set menu.
6. Use the UP or DOWN keys to highlight SET DATE and
press SEL (SOFT KEY 2). Use the UP or DOWN keys to
change the day, month, and year. Press OK (SOFT KEY
2) to save the configuration and return to the Clock Set
menu.
7. Use the UP or DOWN keys to highlight DATE FORMAT
and press SEL (SOFT KEY 2). Use the UP or DOWN
keys to change the parameter setting. Press OK (SOFT
KEY 2) to save the configuration and return to the Clock
Set menu.
8. Press EXIT (SOFT KEY 1) twice to return to the main
menu.

I/O SETTINGS MODE

The I/O Settings mode is used for viewing and editing the I/O
settings.
To configure the I/O settings, perform the following procedure:
1. Select MENU (SOFT KEY 2). The Main menu will be
displayed.
2. Use the UP or DOWN keys to highlight I/O SETTINGS
on the display screen and press ENTER (SOFT KEY 2).
The I/O Settings parameter list will be displayed.
3. Use the UP or DOWN keys to highlight the desired I/O
setting and press SEL (SOFT KEY 2).
4. Use the UP or DOWN keys to select the parameter to
view. Press OK (SOFT KEY 2).
5. Use the UP or DOWN keys to change the parameter set-
ting. Press SAVE (SOFT KEY 2) to save the configura-
tion. Press CANCEL (SOFT KEY 1) to keep the previous
value. Any modifications that are not saved will not be
changed.
6. Press EXIT (SOFT KEY 1) twice to return to the main
menu.

ABB E-Clipse Bypass Operator Control

ACH550 CONTROL PANEL WIRING

The ACH550 control panel is a keypad with an LCD unit that pro-
vides status indication and operator controls for the ACH550
drive, see Fig. 133. In normal operation with the ABB E-Clipse
bypass, the ACH550 should be placed in the Auto model of opera-
tion by pressing the Auto key on the ACH550 control panel. Refer
to the ACH550 User's Manual for additional information on the
ACH550 Control Panel and other aspects of ACH550 operation.
ACH550 CONTROL BOARD
Speed Reference
Process Signal Feedback
Field Wiring
Fig. 133 — ACH550 Control Board Wiring

BYPASS CONTROL KEYPAD AND CONTROL BOARD

WIRING

The ABB E-Clipse bypass has a separated keypad with an LCD
unit that provides status indication and programming of the sys-
tem. This keypad is also used for selecting the Drive or Bypass
mode. The bypass keypad has LED indicating lights that indicate
the status of both the bypass and the drive as well as an LCD dis-
play that provides programming, status and warning/fault indica-
tions. See Fig. 134 for wiring of the E-Clipse bypass control
board.
E-clipse Bypass Control board
6
7
8
9
10
Field Wiring
Factory Wiring
Fig. 134 — E-Clipse Bypass Control Board Wiring
Figure 135 below shows the bypass control keypad and identifies
the functions of the various keys and LED indicating lights.
161
X1
1
Terminal for signal cable shield
2
Analog input 1
3
Analog input common
4
10v / 10ma reference Voltage for potentiometer
5
Analog input 2
6
Analog input Common
1
+24vdc
2
+24vdc
3
Digital input common
4
Ground
5
DI-1 Start / Stop (required field supplied)
DI-2 NOT SELECTED (Damper) Run Enable
DI-3 High priority Safety Factory programmed default
DI-4 NOT SELECTED Emergency Shutdown
DI-5 NOT SELECTED (Low Priortiy Safety)
DI-6 SMOKE CONTROL