Table 15 — Fan Performance — 50P2,P3,P6,P7060 Units with Discharge Plenum and 50P4,P5,P8,P9060 Units
AIRFLOW
0.2
(cfm)
rpm
bhp
12,000
241
1.82
15,000
281
3.14
18,000
323
5.03
21,000
366
7.61
24,000
410
10.97
27,000
455
15.23
30,000
500
20.52
AIRFLOW
1.8
(cfm)
rpm
bhp
12,000
486
7.94
15,000
498
9.90
18,000
518
12.57
21,000
546
16.07
24,000
577
20.49
27,000
611
25.91
30,000
648
32.43
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
3.4
(cfm)
rpm
bhp
12,000
664
16.40
15,000
666
19.12
18,000
672
22.28
21,000
686
26.25
24,000
707
31.23
27,000
30,000
NOTE(S):
a. Fan performance is based on wet coils and clean 2 in. filters.
b. See Component Pressure Drop data table before using Fan Performance tables.
c. To convert bhp to kW, use the formula:
Kilowatts = bhp x 0.746
Motor efficiency
See Physical Data table for motor efficiency.
LEGEND
48/50P3,P5,P7,P9 units only.
bhp
— Brake Horsepower
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.4
0.6
rpm
bhp
rpm
bhp
280
2.41
314
3.04
316
3.87
346
4.61
355
5.92
382
6.80
395
8.66
421
9.69
437
12.20
460
13.39
479
16.65
501
18.00
522
22.11
543
23.64
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.0
2.2
rpm
bhp
rpm
bhp
511
8.91
535
9.91
520
10.93
543
12.01
539
13.66
559
14.78
564
17.23
583
18.42
594
21.74
611
23.00
628
27.26
643
28.63
663
33.90
678
35.38
3.6
3.8
rpm
bhp
rpm
bhp
683
17.55
702
18.70
685
20.39
703
21.69
690
23.64
708
25.02
703
27.67
719
29.11
722
32.71
737
34.20
0.8
1.0
rpm
bhp
rpm
bhp
346
3.72
376
4.47
374
5.38
400
6.19
408
7.68
431
8.58
444
10.71
466
11.73
482
14.55
503
15.71
522
19.33
542
20.64
563
25.14
581
26.61
2.4
2.6
rpm
bhp
rpm
bhp
559
10.94
581
11.99
564
13.11
586
14.26
579
15.95
598
17.15
600
19.64
618
20.90
628
24.31
644
25.63
659
30.03
674
31.44
4.0
rpm
bhp
720
19.87
721
23.01
725
26.44
735
30.59
21
1.2
1.4
rpm
bhp
rpm
bhp
405
5.26
433
6.11
426
7.05
450
7.95
454
9.53
476
10.50
487
12.78
507
13.85
523
16.88
541
18.07
560
21.95
578
23.26
599
28.06
616
29.52
2.8
3.0
rpm
bhp
rpm
bhp
603
13.07
624
14.16
606
15.43
627
16.63
617
18.39
636
19.65
635
22.19
653
23.51
660
26.99
676
28.38
689
32.87
703
34.33
a,b,c
1.6
rpm
bhp
460
7.01
474
8.90
498
11.52
527
14.94
560
19.27
595
24.58
632
30.97
3.2
rpm
bhp
645
15.28
646
17.86
654
20.95
669
24.86
691
29.77
718
35.82