Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 195

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

ITEM
B.V.A
VFD/ACTUATOR CONFIG
B.V.ABP.FS
VFD/Act. Fire Speed/Pos.
B.V.ABP.MN
VFD/Act. Min.Speed/Pos.
B.V.ABP.MX
VFD Maximum Speed
B.V.ABP.1M
BP 1 Actuator Max Pos.
B.V.ABP.2M
BP 2 Actuator Max Pos.
B.V.ABP.CL
BP Hi Cap VFD Clamp Val.
FAN.T
FAN TRACKING CONFIG
FAN.TFT.CF
Fan Track Learn Enable
FAN.TFT.TM
Fan Track Learn Rate
FAN.TFT.ST
Fan Track Initial DCFM
FAN.TFT.MX
Fan Track Max Clamp
FAN.TFT.MN
Fan Track Minimum Clamp
FAN.TFT.AD
Fan Track Max Correction
FAN.TFT.OF
Fan Track Internl EEPROM
FAN.TFT.RM
Fan Track Internal RAM
FAN.TFT.RS
Fan Track Reset Internal
FAN.TSCF.C
Supply Air CFM Config
B.PID
BLDG.PRESS.PID CONFIGS
B.PIDBP.TM
Bldg.Pres.PID Run Rate
B.PIDBP.P
Bldg.Press. Prop. Gain
B.PIDBP.I
Bldg.Press. Integ. Gain
B.PIDBP.D
Bldg.Press. Deriv. Gain
ACT.C
BLDG.PRES. ACTUATOR CFGS
ACT.CBP.1
BLDG.PRES. ACT.1 CONFIGS
ACT.CBP.1SN.1
BP 1 Serial Number 1
ACT.CBP.1SN.2
BP 1 Serial Number 2
ACT.CBP.1SN.3
BP 1 Serial Number 3
ACT.CBP.1SN.4
BP 1 Serial Number 4
ACT.CBP.1C.A.LM
BP1 Cntrl Angle Lo Limit
ACT.CBP.2
BLDG.PRES. ACT.2 CONFIGS
ACT.CBP.2SN.1
BP 2 Serial Number 1
ACT.CBP.2SN.2
BP 2 Serial Number 2
ACT.CBP.2SN.3
BP 2 Serial Number 3
ACT.CBP.2SN.4
BP 2 Serial Number 4
ACT.CBP.2C.A.LM
BP2 Cntrl Angle Lo Limit
PG.EN
Prognostics BP Enable
PG.DB
Prognostics BP Deadband
D.LV.T
COOL/HEAT SETPT. OFFSETS
L.H.ON
Dmd Level Lo Heat On
H.H.ON
Dmd Level(+) Hi Heat On
L.H.OF
Dmd Level(–) Lo Heat Off
L.C.ON
Dmd Level Lo Cool On
H.C.ON
Dmd Level(+) Hi Cool On
L.C.OF
Dmd Level(–) Lo Cool Off
C.T.LV
Cool Trend Demand Level
H.T.LV
Heat Trend Demand Level
C.T.TM
Cool Trend Time
H.T.TM
Heat Trend Time
DMD.L
DEMAND LIMIT CONFIG.
DM.L.S
Demand Limit Select
D.L.20
Demand Limit at 20 ma
SH.NM
Loadshed Group Number
SH.DL
Loadshed Demand Delta
SH.TM
Maximum Loadshed Time
D.L.S1
Demand Limit Sw.1 Setpt.
D.L.S2
Demand Limit Sw.2 Setpt.
IAQ
INDOOR AIR QUALITY CFG.
DCV.C
DCV ECONOMIZER SETPOINTS
DCV.CEC.MN
Economizer Min.Position
DCV.CIAQ.M
IAQ Demand Vent Min.Pos.
DCV.CO.C.MX
Economizer Min.Flow
DCV.CO.C.MN
IAQ Demand Vent Min.Flow
DCV.CO.C.DB
Econ.Min.Flow Deadband
AQ.CF
AIR QUALITY CONFIGS
AQ.CFIQ.A.C
IAQ Analog Sensor Config
AQ.CFIQ.A.F
IAQ 4-20 ma Fan Config
AQ.CFIQ.I.C
IAQ Discrete Input Config
AQ.CFIQ.I.F
IAQ Disc.In. Fan Config
AQ.CFOQ.A.C
OAQ 4-20ma Sensor Config
AQ.SP
AIR QUALITY SETPOINTS
AQ.SPIQ.O.P
IAQ Econo Override Pos.
AQ.SPIQ.O.C
IAQ Override Flow
AQ.SPDAQ.L
Diff.Air Quality LoLimit
AQ.SPDAQ.H
Diff. Air Quality HiLimit
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
Table H — MODE — CONFIGURATION (cont)
EXPANSION
0 to 100
0 to 50
50 to 100
85 to 100
85 to 100
5 to 25
Yes/No
5 to 60
–20000 to 20000
0 to 20000
–20000 to 0
0 to 20000
–20000 to 20000
–20000 to 20000
Yes/No
1 to 2 (multi-text strings)
5 to 120
0 to 5
0 to 2
0 to 5
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
Disable/Enable
0 to 1
–1 to 2
0.5 to 20.0
0.5 to 2.0
–1 to 2
0.5 to 20.0
0.5 to 2.0
0.1 to 5.0
0.1 to 5.0
30 to 600
30 to 600
0 to 3 (multi-text strings)
0 to 100
0 to 99
0 to 60
0 to 120
0 to 100
0 to 100
0 to 100
0 to 100
0 to 20000
0 to 20000
200 to 1000
0 to 4 (multi-text strings)
0 to 2 (multi-text strings)
0 to 2 (multi-text strings)
0 to 2 (multi-text strings)
0 to 2 (multi-text strings)
0 to 100
0 to 31000
0 to 1000
100 to 2000
RANGE
UNITS
%
BLDGPFSO
%
BLDGPMIN
%
BLDGPMAX
%
BP1SETMX
%
BP2SETMX
%
BLDGCLMP
DCFM_CFG
min
DCFMRATE
CFM
DCFMSTRT
CFM
DCFM_MAX
CFM
DCFM_MIN
CFM
DCFM_ADJ
CFM
DCFM_OFF
CFM
DCFM_RAM
DCFMRSET
SCFM_CFG
sec
BPIDRATE
BLDGP_PG
BLDGP_IG
BLDGP_DG
BP_1_SN1
BP_1_SN2
BP_1_SN3
BP_1_SN4
BP1_CALM
BP_2_SN1
BP_2_SN2
BP_2_SN3
BP_2_SN4
BP2_CALM
PG_BP_EN
PG_BP_DB
^F
DMDLHON
^F
DMDHHON
^F
DMDLHOFF
^F
DMDLCON
^F
DMDHCON
^F
DMDLCOFF
^F
CTRENDLV
^F
HTRENDLV
sec
CTRENDTM
sec
HTRENDTM
DMD_CTRL
%
DMT20MA
SHED_NUM
%
SHED_DEL
min
SHED_TIM
%
DLSWSP1
%
DLSWSP2
%
ECONOMIN
%
IAQMINP
CFM
OACFMMAX
CFM
OACFMMIN
CFM
OACFM_DB
IAQANCFG
IAQANFAN
IAQINCFG
IAQINFAN
OAQANCFG
%
IAQOVPOS
CFM
IAQOVCFM
DAQ_LOW
DAQ_HIGH
195
CCN POINT
DEFAULT
100
83
0
83
100
83
100
84
100
84
10
84
No
84
15
84
2000
84
4000
84
–1000
84
1000
85
0
85
0
85
No
85
1
85
10
85
0.5
85
0.5
85
0.3
85
0
84, 86
0
84, 86
0
84, 86
0
84, 86
35
84, 86
0
84, 86
0
84, 86
0
84, 86
0
84, 86
35
84, 86
1.5
35, 54, 64
0.5
54, 64
1
35, 54, 65
1.5
54, 64
0.5
54, 64
1
54, 64
0.1
54, 64
0.1
54, 65
120
54, 64
120
54, 65
0
42, 47, 58
100
42, 58
0
58
0
58
60
58
80
42, 58
50
42, 58
5
36, 42, 89, 90
0
36, 42, 89, 90
2000
36, 42, 89
0
36, 42, 89
400
89
0
43, 88
0
43, 88-89
0
43, 47, 88-89
0
43, 88-90
0
88
100
43, 88-90
10000
88
100
88-90
700
88-90
PAGE NO.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Weathermaster 50p030-100

Table of Contents