Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 22

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

Table 16 — Fan Performance — 50P2,P3,P6,P7070 Units with Discharge Plenum and 50P4,P5,P8,P9070 Units
AIRFLOW
0.2
(cfm)
rpm
bhp
14,000
268
2.64
17,500
316
4.67
21,000
366
7.61
24,500
417
11.61
28,000
470
16.88
30,000
500
20.52
AIRFLOW
1.8
(cfm)
rpm
bhp
14,000
493
9.17
17,500
515
12.07
21,000
546
16.07
24,500
583
21.32
28,000
623
27.96
30,000
648
32.43
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
3.4
(cfm)
rpm
bhp
14,000
665
18.18
17,500
671
21.70
21,000
686
26.24
24,500
711
32.17
28,000
30,000
NOTE(S):
a. Fan performance is based on wet coils and clean 2 in. filters.
b. See Component Pressure Drop data table before using Fan Performance tables.
c. To convert bhp to kW, use the formula:
Kilowatts = bhp x 0.746
Motor efficiency
See Physical Data table for motor efficiency.
LEGEND
48/50P3,P5,P7,P9 units only.
bhp
— Brake Horsepower
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.4
0.6
rpm
bhp
rpm
bhp
304
3.32
335
4.02
348
5.54
376
6.39
395
8.66
421
9.69
444
12.87
467
14.09
493
18.35
515
19.77
522
22.11
543
23.64
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.0
2.2
rpm
bhp
rpm
bhp
516
10.19
539
11.24
535
13.14
556
14.26
564
17.23
583
18.42
600
22.59
616
23.87
639
29.35
655
30.75
663
33.90
678
35.38
3.6
3.8
rpm
bhp
rpm
bhp
684
19.42
703
20.68
689
23.05
706
24.42
703
27.67
719
29.11
726
33.65
741
35.16
0.8
1.0
rpm
bhp
rpm
bhp
364
4.76
391
5.55
402
7.25
426
8.14
444
10.71
466
11.73
489
15.28
509
16.47
536
21.15
555
22.51
563
25.14
581
26.61
2.4
2.6
rpm
bhp
rpm
bhp
562
12.33
583
13.45
576
15.42
595
16.61
600
19.64
618
20.90
633
25.18
649
26.53
670
32.18
685
33.63
4.0
rpm
bhp
721
21.95
724
25.82
735
30.59
22
1.2
1.4
rpm
bhp
rpm
bhp
418
6.39
444
7.27
449
9.06
472
10.03
487
12.78
507
13.85
529
17.66
547
18.86
573
23.87
590
25.22
599
28.06
616
29.52
2.8
3.0
rpm
bhp
rpm
bhp
605
14.60
625
15.77
615
17.84
634
19.09
635
22.19
653
23.51
664
27.89
680
29.29
699
35.09
a,b,c
1.6
rpm
bhp
468
8.20
493
11.03
527
14.94
565
20.08
607
26.59
632
30.97
3.2
rpm
bhp
645
16.96
652
20.39
669
24.86
695
30.71

Advertisement

Table of Contents
loading

This manual is also suitable for:

Weathermaster 50p030-100

Table of Contents