Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 247

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

SPECIFICATION
Cable
Conductor
Insulation
Color Code
Twist Lay
Shielding
Jacket
DC Resistance
Capacitance
Characteristic Impedance
Weight
UL Temperature Rating
Voltage
Listing
LEGEND
AWG
— American Wire Gauge
CL2P
— Class 2 Plenum Cable
DC
— Direct Current
FEP
— Fluorinated Ethylene Polymer
NEC
— National Electrical Code
O.D.
— Outside Diameter
TC
— Tinned Copper
UL
— Underwriters Laboratories
Table AT — Open System Wiring Specifications and Recommended Vendors
Wire Type
22 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam
FEP, plenum rated. See MS/TP Installation Guide for 
specifications.
MS/TP
Network (RS-485)
24 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam
FEP, plenum rated. See MS/TP Installation Guide
for specifications.
Rnet
4 conductor, unshielded, CMP, 18 AWG, plenum rated.
LEGEND
AWG
— American Wire Gauge
CL2P
— Class 2 Plenum Cable
CMP
— Communications Plenum Rated
FEP
— Fluorinated Ethylene Polymer
TC
— Tinned Copper
LED
Lights when power is being supplied to the controller. The UPC Open controller is protected by internal solid-state polyswitches on the incoming power
Power
and network connections. These polyswitches are not replaceable and will reset themselves if the condition that caused the fault returns to normal.
Rx
Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1 and 2.
Tx
Lights when the controller transmits data to the network segment; there is an Tx LED for Ports 1 and 2.
Run
Lights based on controller status. See Table AV.
Error
Lights based on controller status. See Table AV.
Table AV — Run and Error LEDs Controller and Network Status Indication
RUN LED
Off
2 flashes, alternating with Run LED
2 flashes per second
3 flashes, then off
1 flash per second
On
On
5 flashes per second
Off
7 flashes per second
7 flashes per second, alternating with Run LED
14 flashes per second
14 flashes per second, alternating with Run LED
APPENDIX G — UPC OPEN CONTROLLER (CONT)
Table AS — MS/TP Wiring Recommendations
Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable
22 or 24 AWG stranded copper (tin plated)
Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.
Black/White
2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal
Aluminum/Mylar shield with 24 AWG TC drain wire
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.
15.2 Ohms/1000 feet (50 Ohms/km) nominal
12.5 pF/ft (41 pF/meter) nominal conductor to conductor
100 Ohms nominal
12 lb/1000 feet (17.9 kg/km)
SmokeGard 167°F (75°C)
Halar –40°F to 302°F (–40°C to 150°C)
300 Vac, power limited
UL: NEC CL2P, or better
WIRING SPECIFICATIONS
Description
Table AU — LED Status Indicators
ERROR LED
RECOMMMENDATION
RECOMMENDED VENDORS AND PART NUMBERS
Connect Air
International
W221P-22227
W241P-2000F
W184C-2099BLB
STATUS
Normal
Five minute auto-restart delay after system error
Controller has just been formatted
Controller is alone on the network
Exec halted after frequent system errors or control programs halted
Exec start-up aborted, Boot is running
Firmware transfer in progress, Boot is running
Ten second recovery period after brownout
Brownout
247
Contractors
Belden
RMCORP
Wire and Cable
25160PV
CLP0520LC
82841
25120-OR
6302UE
21450
CLP0442
STATUS