ITEM
IAQ
INDOOR AIR QUALITY CFG.
DCV.C
DCV ECONOMIZER SETPOINTS
DCV.CEC.MN
Economizer Min.Position
DCV.CIAQ.M
IAQ Demand Vent Min.Pos.
DCV.CO.C.MX
Economizer Min.Flow
DCV.CO.C.MN
IAQ Demand Vent Min.Flow
DCV.CO.C.DB
Econ.Min.Flow Deadband
AQ.CF
AIR QUALITY CONFIGS
AQ.CFIQ.A.C
IAQ Analog Sensor Config
AQ.CFIQ.A.F
IAQ 4-20 ma Fan Config
AQ.CFIQ.I.C
IAQ Discrete Input Config
AQ.CFIQ.I.F
IAQ Disc.In. Fan Config
AQ.CFOQ.A.C
OAQ 4-20ma Sensor Config
AQ.SP
AIR QUALITY SETPOINTS
AQ.SPIQ.O.P
IAQ Econo Override Pos.
AQ.SPIQ.O.C
IAQ Override Flow
AQ.SPDAQ.L
Diff.Air Quality LoLimit
AQ.SPDAQ.H
Diff. Air Quality HiLimit
AQ.SPD.F.OF
DAQ PPM Fan Off Setpoint
AQ.SPD.F.ON
DAQ PPM Fan On Setpoint
AQ.SPIAQ.R
Diff. AQ Responsiveness
AQ.SPOAQ.L
OAQ Lockout Value
AQ.SPOAQ.U
User Determined OAQ
AQ.S.R
AIR QUALITY SENSOR RANGE
AQ.S.RIQ.R.L
IAQ Low Reference
AQ.S.RIQ.R.H
IAQ High Reference
AQ.S.ROQ.R.L
OAQ Low Reference
AQ.S.ROQ.R.H
OAQ High Reference
IAQ.P
IAQ PRE-OCCUPIED PURGE
IAQ.PIQ.PG
IAQ Purge
IAQ.PIQ.P.T
IAQ Purge Duration
IAQ.PIQ.P.L
IAQ Purge LoTemp Min Pos
IAQ.PIQ.P.H
IAQ Purge HiTemp Min Pos
IAQ.PIQ.L.O
IAQ Purge OAT Lockout
HUMD
HUMIDITY CONFIGURATION
HM.CF
Humidifier Control Cfg.
HM.SP
Humidifier Setpoint
H.PID
HUMIDIFIER PID CONFIGS
H.PIDHM.TM
Humidifier PID Run Rate
H.PIDHM.P
Humidifier Prop. Gain
H.PIDHM.I
Humidifier Integral Gain
H.PIDHM.D
Humidifier Deriv. Gain
ACT.C
HUMIDIFIER ACTUATOR CFGS
ACTCSN.1
Humd Serial Number 1
ACTCSN.2
Humd Serial Number 2
ACTCSN.3
Humd Serial Number 3
ACTCSN.4
Humd Serial Number 4
ACTCC.A.LM
Humd Ctrl Angle Lo Limit
DEHU
DEHUMIDIFICATION CONFIG.
D.SEL
Dehumidification Config
D.SEN
Dehumidification Sensor
D.EC.D
Econ disable in DH mode?
D.V.CF
Vent Reheat Setpt Select
D.V.RA
Vent Reheat RAT offset
D.V.HT
Vent Reheat Setpoint
D.C.SP
Dehumidify Cool Setpoint
D.RH.S
Dehumidify RH Setpoint
HZ.RT
Humidimizer Adjust Rate
HZ.PG
Humidimizer Prop. Gain
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
EXPANSION
RANGE
0 to 100%
0 to 100%
0 to 20000 CFM
0 to 20000 CFM
200 to 1000 CFM
0 to 4 (multi-text strings)
0 to 2 (multi-text strings)
0 to 2 (multi-text strings)
0 to 2 (multi-text strings)
0 to 2 (multi-text strings)
0 to 100%
0 to 31000 CFM
0 to 1000
100 to 2000
0 to 2000
0 to 2000
–5 to 5
0 to 2000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
Yes/No
5 to 60 min
0 to 100%
0 to 100%
35 to 70 dF
0 to 4
0 to 100%
10 to 120 sec
0 to 5
0 to 5
0 to 5
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 3 (multi-text strings)
1 to 3 (multi-text strings)
Yes/No
0 to 1 (multi-text strings)
0 to 8 delta F
55 to 95 dF
40 to 55 dF
10 to 90%
5-120 sec
0-10
CL-24
DEFAULT
SETTING
5
0
2000
0
400
0
0
0
0
0
100
10000
100
700
200
400
0
0
400
0
2000
0
2000
No
15
10
35
50
0
40
30
1
0.3
0.3
0
0
0
0
85
0
1
Yes
0
0
70
45
55
30
0.8