ITEM
IAQ
INDOOR AIR QUALITY CFG.
DCV.C
DCV ECONOMIZER SETPOINTS
DCV.CEC.MN
Economizer Min.Position
DCV.CIAQ.M
IAQ Demand Vent Min.Pos.
DCV.CO.C.MX
Economizer Min.Flow
DCV.CO.C.MN
IAQ Demand Vent Min.Flow
DCV.CO.C.DB
Econ.Min.Flow Deadband
AQ.CF
AIR QUALITY CONFIGS
AQ.CFIQ.A.C
IAQ Analog Sensor Config
AQ.CFIQ.A.F
IAQ 4-20 ma Fan Config
AQ.CFIQ.I.C
IAQ Discrete Input Config
AQ.CFIQ.I.F
IAQ Disc.In. Fan Config
AQ.CFOQ.A.C
OAQ 4-20ma Sensor Config
AQ.SP
AIR QUALITY SETPOINTS
AQ.SPIQ.O.P
IAQ Econo Override Pos.
AQ.SPIQ.O.C
IAQ Override Flow
AQ.SPDAQ.L
Diff.Air Quality LoLimit
AQ.SPDAQ.H
Diff. Air Quality HiLimit
AQ.SPD.F.OF
DAQ PPM Fan Off Setpoint
AQ.SPD.F.ON
DAQ PPM Fan On Setpoint
AQ.SPIAQ.R
Diff. AQ Responsiveness
AQ.SPOAQ.L
OAQ Lockout Value
AQ.SPOAQ.U
User Determined OAQ
AQ.S.R
AIR QUALITY SENSOR RANGE
AQ.S.RIQ.R.L
IAQ Low Reference
AQ.S.RIQ.R.H
IAQ High Reference
AQ.S.ROQ.R.L
OAQ Low Reference
AQ.S.ROQ.R.H
OAQ High Reference
IAQ.P
IAQ PRE-OCCUPIED PURGE
IAQ.PIQ.PG
IAQ Purge
IAQ.PIQ.P.T
IAQ Purge Duration
IAQ.PIQ.P.L
IAQ Purge LoTemp Min Pos
IAQ.PIQ.P.H
IAQ Purge HiTemp Min Pos
IAQ.PIQ.L.O
IAQ Purge OAT Lockout
HUMD
HUMIDITY CONFIGURATION
HM.CF
Humidifier Control Cfg.
HM.SP
Humidifier Setpoint
H.PID
HUMIDIFIER PID CONFIGS
H.PIDHM.TM
Humidifier PID Run Rate
H.PIDHM.P
Humidifier Prop. Gain
H.PIDHM.I
Humidifier Integral Gain
H.PIDHM.D
Humidifier Deriv. Gain
ACT.C
HUMIDIFIER ACTUATOR CFGS
ACTCSN.1
Humd Serial Number 1
ACTCSN.2
Humd Serial Number 2
ACTCSN.3
Humd Serial Number 3
ACTCSN.4
Humd Serial Number 4
ACTCC.A.LM
Humd Ctrl Angle Lo Limit
DEHU
DEHUMIDIFICATION CONFIG.
D.SEL
Dehumidification Config
D.SEN
Dehumidification Sensor
D.EC.D
Econ disable in DH mode?
D.V.CF
Vent Reheat Setpt Select
D.V.RA
Vent Reheat RAT offset
D.V.HT
Vent Reheat Setpoint
D.C.SP
Dehumidify Cool Setpoint
D.RH.S
Dehumidify RH Setpoint
HZ.RT
Humidimizer Adjust Rate
HZ.PG
Humidimizer Prop. Gain
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
EXPANSION
RANGE
0 to 100%
0 to 100%
0 to 20000 CFM
0 to 20000 CFM
200 to 1000 CFM
0 to 4 (multi-text strings)
0 to 2 (multi-text strings)
0 to 2 (multi-text strings)
0 to 2 (multi-text strings)
0 to 2 (multi-text strings)
0 to 100%
0 to 31000 CFM
0 to 1000
100 to 2000
0 to 2000
0 to 2000
–5 to 5
0 to 2000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
Yes/No
5 to 60 min
0 to 100%
0 to 100%
35 to 70 dF
0 to 4
0 to 100%
10 to 120 sec
0 to 5
0 to 5
0 to 5
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 3 (multi-text strings)
1 to 3 (multi-text strings)
Yes/No
0 to 1 (multi-text strings)
0 to 8 delta F
55 to 95 dF
40 to 55 dF
10 to 90%
5-120 sec
0-10
CL-24
DEFAULT
SETTING
5
0
2000
0
400
0
0
0
0
0
100
10000
100
700
200
400
0
0
400
0
2000
0
2000
No
15
10
35
50
0
40
30
1
0.3
0.3
0
0
0
0
85
0
1
Yes
0
0
70
45
55
30
0.8