Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 207

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

TABLE
EDTR
EDT Reset Configuration
Reset Ratio
Reset Limit
EDT 4-20 ma Reset Input
GSCONFIG
Unit Size (30 - 100)
Machine Control Type
A1 is a Digital Scroll
Dehumidification Config
Outdoor VFD Enable
Outdoor VFD PI Run Rate
Outdoor VFD Prop. Gain
Outdoor VFD Integ. Time
Outdoor VFD Anti-Windup
Outdoor VFD SCT DeadBand
Outdoor VFD Dehum-RH SPD
OV MinStartSpeed Low Amb
OV Prop. Gain at Low Amb
OV Intg. Time at Low Amb
Outdoor VFD MvgAvgFltrPt
HEAT
Heating Control Type
Heating Supply Air Setpt
Occupied Heating Enabled
MBB Sensor Heat Relocate
Staged Heat Type
Max Cap Change per Cycle
St.Ht DB min.dF/PID Rate
St.Heat Temp. Dead Band
Heat Rise dF/sec Clamp
LAT Limit Config
Limit Switch Switch Monitoring?
Limit Switch High Temp
Limit Switch Low Temp
Heat Control Prop. Gain
Heat Control Derv. Gain
Heat PID Rate Config
Hydronic Ctl.Prop. Gain
Hydronic Ctl.Integ. Gain
Hydronic Ctl.Derv. Gain
Hydronic PID Rate Config
Hydronic Ht.Serial Num.1
Hydronic Ht.Serial Num.2
Hydronic Ht.Serial Num.3
Hydronic Ht.Serial Num.4
Hydr.Ht.Ctl.Ang.Lo Limit
HUMD
Humidifier Control Cfg.
Humidifier Setpoint
Humidifier PID Run Rate
Humidifier Prop. Gain
Humidifier Integral Gain
Humidifier Deriv. Gain
Humd Serial Number 1
Humd Serial Number 2
Humd Serial Number 3
Humd Serial Number 4
Humd Ctrl Angle Lo Limit
IAQ_
Economizer Min.Position
IAQ Demand Vent Min.Pos.
Economizer Min.Flow
IAQ Demand Vent Min.Flow
Econ.Min.Flow Deadband
IAQ Analog Sensor Config
IAQ 4-20 ma Fan Config
IAQ Discrete Input Config
IAQ Disc.In. Fan Config
OAQ 4-20ma Sensor Config
IAQ Econo Override Pos.
IAQ Override flow
Diff.Air Quality LoLimit
Diff. Air Quality HiLimit
DAQ PPM Fan Off Setpoint
APPENDIX B — CCN TABLES (CONT)
Table O — SERVICE-CONFIG TABLES (cont)
DISPLAY NAME
RANGE
UNITS
0 to 3
0 to 10
0 to 20
^F
Enable/Disable
No/Yes
No/Yes
secs
0 to 5
0.5 to 200
secs
0.1 to 1
0 to 20
degF
0 to 100
%
0 to 100
%
0 to 5
0.5 to 200
secs
0 to 5
0 to 5
80 to 120
dF
Yes/No
Yes/No
0 to 8
5 to 45
0 to 5
0 to 5
^F
0.05 to 0.2
0 to 20
^F
Yes/No
110 to 180
dF
100 to 170
dF
0 to 1.5
0 to 1.5
30 to 300
sec
0 to 1.5
0 to 1.5
0 to 1.5
15 to 300
sec
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 4
0 to 100
%
10 to 120
sec
0 to 5
0 to 5
0 to 5
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 100
%
0 to 100
%
0 to 20000
CFM
0 to 20000
CFM
200 to 1000
CFM
0 to 4
0 to 2
0 to 2
0 to 2
0 to 2
0 to 100
%
0 to 31000
CFM
0 to 1000
100 to 2000
0 to 2000
207
POINT NAME
DEFAULT
EDRSTCFG
2
RTIO
3
LIMT
10
EDTRSENS
Disable
UNITSIZE
CTRLTYPE
DIGCMPA1
DHSELECT
OV_ENA
OV_RATE
OV_PG
0.7
OV_TI
30
OV_AU
0.8
OV_SCTDB
5
OV_RH
67
OV_STMIN
30
OV_PG_LA
0.1
OV_TI_LA
30
OV_MAFP
5
HEATTYPE
0
SASPHEAT
85
HTOCCENA
No
HTLATMON
No
HTSTGTYP
0
HTCAPMAX
45
HT_MR_DB
0.5
HT_SG_DB
2
HTSGRISE
0.06
HTLATLIM
10
HTLIMMON
Yes
HT_LIMHI
170
HT_LIMLO
160
HT_PGAIN
1
HT_DGAIN
1
HTSGPIDR
90
HW_PGAIN
1
HW_IGAIN
1
HW_DGAIN
1
HOTWPIDR
90
HTCL_SN1
0
HTCL_SN2
0
HTCL_SN3
0
HTCL_SN4
0
HTCLCALM
85
HUMD_CFG
0
HUSP
40
HUMDRATE
30
HUMID_PG
1
HUMID_IG
0.3
HUMID_DG
0.3
HUMD_SN1
0
HUMD_SN2
0
HUMD_SN3
0
HUMD_SN4
0
HUMDCALM
85
ECONOMIN
5
IAQMINP
0
OACFMMAX
2000
OACFMMIN
0
OACFM_DB
400
IAQANCFG
0
IAQANFAN
0
IAQINCFG
0
IAQINFAN
0
OAQANCFG
0
IAQOVPOS
100
IAQOVCFM
10000
DAQ_LOW
100
DAQ_HIGH
700
DAQFNOFF
200

Advertisement

Table of Contents
loading

This manual is also suitable for:

Weathermaster 50p030-100

Table of Contents