Table 111 — Control Expansion Module (CEM) Inputs and Outputs
POINT NAME
INPUTS
DHDISCIN
Dehumidify Switch Input
DMD_SW1
Demand Limit 1 — Redline
DMD_SW2
Demand Limit 2 — Loadshed
PRES
Pressurization
EVAC
Evacuation
PURG
Purge
IAQIN
IAQ Discrete Input
OACFM
Outside Air CFM — 4-20 (VAV)
OARH
Outside Air RH (VAV)
SPRH
Space RH
RARH
Return Air RH
DMDLMTMA
Demand Limit — 4-20
SATRESMA
SAT Reset 4-20 (VAV)
OAQ
OAQ — 4-20
Not Used
Not Used
Not Used
Table 112 — Compressor Expansion Board (CXB) Inputs and Outputs
POINT NAME
INPUTS
CSB_A3
Compressor A3 Feedback
CSB_B3
Compressor B3 Feedback
Not Used
Not Used
Not Used
Not Used
OUTPUTS
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
CMPB3
Compressor B3 Relay
CMPA3
Compressor A3 Relay
Table 113 — Expansion Valve Control Board (EXV) Inputs and Outputs
POINT NAME
POINT DESCRIPTION
INPUTS
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
OUTPUTS
COND_EXV
Humidimizer Control Valve 1
BYP_EXV
Humidimizer Control Valve 2
CEBD430351
J1
J2
LEN
J4
J3
STATUS
J5
J6
GREEN LED -
RED LED - STATUS
LEN (LOCAL EQUIPMENT NETWORK)
Fig. 34 — Controls Expansion Board (CEM)
POINT DESCRIPTION
POINT DESCRIPTION
Thermistor
Thermistor
Thermistor
Thermistor
Transducer (4-20 mA)
Transducer (4-20 mA)
Stepper Motor
Stepper Motor
J7
ADDRESS
DIP SWITCH (ALL ON)
TYPE OF I/O
Switch
DI 1
Switch
DI 2
Switch
DI 3
Switch
DI 4
Switch
DI 5
Switch
DI 6
Switch
DI 7
4 to 20 mA
AN7
4 to 20 mA
AN8
4 to 20 mA
AN9
4 to 20 mA
AN10
Thermistor
AN1
Thermistor
AN2
Thermistor
AN3
Thermistor
AN4
Thermistor
AN5
Thermistor
AN6
TYPE OF I/O
Digital Input
DIG1
Digital Input
DIG2
Digital Input
DIG3
Digital Input
DIG4
Relay
RLY1
Relay
RLY2
Relay
RLY3
Relay
RLY4
Relay
RLY5
Relay
RLY6
TYPE OF I/O
I/O POINT NAME
AN1
AN2
AN3
AN4
AN5
AN6
EXV-1
EXV-2
151
TEST 2
I/O POINT NAME
CONNECTOR PIN NO.
J7, 1-2
J7, 3-4
J7, 5-6
J7, 7-8
J7, 9-10
J7, 11-12
J7, 13-14
J6, 1-3
J6, 4-6
J6, 7-9
J6, 10-12
J5, 1-2
J5, 3-4
J5, 5-6
J5, 7-8
J5, 9-10
J5, 11-12
I/O POINT NAME
CONNECTOR PIN NO.
J9, 10-12
J9, 7-9
J9, 4-6
J9, 1-3
J6, 1-2
J6, 3-4
J6, 5-6
J6, 7-8
J6, 9-11
J6, 12-14
CONNECTOR PIN NO.
J5, 5-6
J5, 7-8
J5, 9-10
J5, 11-12
J5, 1-2
J5, 3-4
J6, 1-5
J7, 1-5