Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 208

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

TABLE
IAQ_ (cont)
DAQ PPM Fan On Setpoint
Diff. AQ Responsiveness
OAQ Lockout Value
User determined OAQ
IAQ Low Reference
IAQ High Reference
OAQ Low Reference
OAQ High Reference
IAQ Purge
IAQ Purge Duration
IAQ Purge LoTemp Min Pos
IAQ Purge HiTemp Min Pos
IAQ Purge OAT Lockout
ECON POS AT MIN VFD SPEED
ECON POS AT MAX VFD SPEED
OV_CFG
OV-A Nominal Motor Volts
OV-A Nominal Motor Amps
OV-A Nominal Motor Freq
OV-A Nominal Motor rpm
OV-A Nominal Motor HPwr
OV-A Motor Direction
OV-A Acceleration Time
OV-A Deceleration Time
OV-A Switching Frequency
OV-B Nominal Motor Volts
OV-B Nominal Motor Amps
OV-B Nominal Motor Freq
OV-B Nominal Motor rpm
OV-B Nominal Motor HPwr
OV-B Motor Direction
OV-B Acceleration Time
OV-B Deceleration Time
OV-B Switching Frequency
SP__
Static Pressure Control
Staged Air Volume Control
Static Pressure Sensor
Static Press. Low Range
Static Press. High Range
Static Pressure Setpoint
VFD Minimum Speed
VFD Maximum Speed
VFD MinSpeed in HeatMode 75%
VFD MaxSpeed in HeatMode 100%
VFD Fire Speed Over.
Stat. Pres. Reset Config
SP Reset Ratio
SP Reset Limit
SP Reset Econo. Position
Stat.Pres.PID Run Rate
Static Press. Prop. Gain
Static Press. Intg. Gain
Static Press. Derv. Gain
SWLG
Filter Status Inpt-Clean
IGC Feedback - Off
RemSw Off-Unoc-Strt-NoOv
Enthalpy Input - Low
Fan Status Sw. - Off
Dmd.Lmt.Sw.1 - Off
Dmd.Lmt.Sw.2 - Off
IAQ Disc.Input - Low
Fire Shutdown - Off
Press. Switch - Off
Evacuation Sw. - Off
Smoke Purge Sw. - Off
Dehumidify Sw. - Off
APPENDIX B — CCN TABLES (CONT)
Table O — SERVICE-CONFIG TABLES (cont)
DISPLAY NAME
RANGE
UNITS
0 to 2000
–5 to 5
0 to 2000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
Yes/No
5 to 60
min
0 to 100
%
0 to 100
%
35 to 70
dF
0 to 100
%
0 to 100
%
0 to 999
volts
0 to 999
amps
10 to 500
50 to 30000
0 to 500
0=F, 1=R
0 to 1800
secs
0 to 1800
secs
0 to 3
0 to 999
volts
0 to 999
amps
10 to 500
50 to 30000
0 to 500
0=F, 1=R
0 to 1800
secs
0 to 1800
secs
0 to 3
Enable/Disable
Enable/Disable
Enable/Disable
–10 to 0
0 to 10
0 to 5
"H2O
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
0 to 4 (multi-text strings)
0.00 to 2.00
0.00 to 2.00
0 to 100
%
5 to 120
sec
0 to 5
0 to 2
0 to 5
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
208
POINT NAME
DEFAULT
DAQFNON
400
IAQREACT
0
OAQLOCK
0
OAQ_USER
400
IAQREFL
0
IAQREFH
2000
OAQREFL
0
OAQREFH
2000
IAQPURGE
No
IAQPTIME
15
IAQPLTMP
10
IAQPHTMP
35
IAQPNTLO
50
EPOSMNFS
5
EPOSMXFS
5
OVA_NVLT
OVA_NAMP
OVA_NFRQ
OVA_Nrpm
OVA_NPWR
OVA_MDIR
OVA_ACCL
OVA_DECL
OVA_SWFQ
OVB_NVLT
OVB_NAMP
OVB_NFRQ
OVB_Nrpm
OVB_NPWR
OVB_MDIR
OVB_ACCL
OVB_DECL
OVB_SWFQ
STATICFG
Disable
STGAVCFG
Disable
SPSENS
Disable
SP_LOW
0
SP_HIGH
5
SPSP
1.5
STATPMIN
10
STATPMAX
100
HTSPMIN
HTSPMAX
STATPFSO
100
SPRSTCFG
0
SPRRATIO
0.20
SPRLIMIT
0.75
ECONOSPR
5
SPIDRATE
15
STATP_PG
0.5
STATP_IG
0.5
STATP_DG
0.3
FLTSLOGC
Open
GASFANLG
Open
RMTINLOG
Open
ENTHLOGC
Close
SFSLOGIC
Open
DMD_SW1L
Open
DMD_SW2L
Open
IAQINLOG
Open
FSDLOGIC
Open
PRESLOGC
Open
EVACLOGC
Open
PURGLOGC
Open
DHDISCLG
Open