Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 84

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

ITEM
BP
BUILDING PRESS. CONFIGS
BP.CF
Building Press. Config
BP.S
Building Pressure Sensor
BP.R
Bldg. Press. (+/-) Range
BP.SP
Building Pressure Setp.
BP.SO
BP Setpoint Offset
BP.P1
Power Exhaust On Setp.1
BP.P2
Power Exhaust On Setp.2
B.V.A
VFD/ACTUATOR CONFIG
BP.FS
VFD/Act. Fire Speed/Pos.
BP.MN
VFD/Act. Min.Speed/Pos.
BP.MX
VFD Maximum Speed
BP.1M
BP 1 Actuator Max Pos.
BP.2M
BP 2 Actuator Max Pos.
BP.CL
BP Hi Cap VFD Clamp Val.
FAN.T
FAN TRACKING CONFIG
FT.CF
Fan Track Learn Enable
FT.TM
Fan Track Learn Rate
FT.ST
Fan Track Initial DCFM
FT.MX
Fan Track Max Clamp
FT.MN
Fan Track Minimum Clamp
FT.AD
Fan Track Max Correction
FT.OF
Fan Track Internl EEPROM
FT.RM
Fan Track Internal RAM
FT.RS
Fan Track Reset Internal
SCF.C
Supply Air CFM Config
B.PID
BLDG.PRESS.PID CONFIGS
BP.TM
Bldg.Pres.PID Run Rate
BP.P
Bldg.Press. Prop. Gain
BP.I
Bldg.Press. Integ. Gain
BP.D
Bldg.Press. Deriv. Gain
ACT.C
BLDG.PRES. ACTUATOR CFGS
BP.1
BLDG.PRES. ACT.1 CONFIGS
SN.1
BP 1 Serial Number 1
SN.2
BP 1 Serial Number 2
SN.3
BP 1 Serial Number 3
SN.4
BP 1 Serial Number 4
C.A.LM
BP1 Cntrl Angle Lo Limit
BP.2
BLDG.PRES. ACT.2 CONFIGS
SN.1
BP 2 Serial Number 1
SN.2
BP 2 Serial Number 2
SN.3
BP 2 Serial Number 3
SN.4
BP 2 Serial Number 4
C.A.LM
BP2 Cntrl Angle Lo Limit
NOTE(S):
a. Some configurations are model number dependent.
BP 1 Actuator Max Pos. (BP.1M)
For BP.CF = 2, this configuration is the maximum actuator no. 1
position during building pressure control.
BP 2 Actuator Max Pos. (BP.2M)
For BP.CF = 2, this configuration is the maximum actuator no. 2
position during building pressure control.
BP Hi Cap VFD Clamp Val. (BP.CL)
For BP.CF = 4, this configuration is a limit that creates a deadband
which controls the action of the second power exhaust relay.
Fan Track Learn Enable (FT.CF)
WARNING
Fan tracking learning is a system dependent operation and
should not be used with default values.
Do not use the fan track learning disable setting unless a system
air balance has been done to determine the correct FT.MX and
FT.MN values. Allowing these values to run without proper
clamps can cause system damage inside the building.
Table 68 — Building Pressure Configuration
EXPANSION
0 to 6
Enable/Disable
0.10 to 0.25
–0.25 to 0.25
0 to 0.5
0 to 100
0 to 100
0 to 100
0 to 50
50 to 100
85 to 100
85 to 100
5 to 25
Yes/No
5 to 60
–20000 to 20000
0 to 20000
–20000 to 0
0 to 20000
–20000 to 20000
–20000 to 20000
Yes/No
1 to 2
5 to 120
0 to 5
0 to 2
0 to 5
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
RANGE
UNITS
"H2O
"H2O
"H2O
%
%
%
%
%
%
%
%
min
CFM
CFM
CFM
CFM
CFM
CFM
sec
For BP.CF = 5, this return/exhaust control configuration selects
whether the fan tracking algorithm will make corrections over
time and add a learned offset to FT.ST. If this configuration is set
to No, the unit will try to control the delta cfm value between the
supply and return VFDs only based on FT.ST.
Fan Track Initial DCFM (FT.ST)
For BP.CF = 5, this return/exhaust control configuration is the
start point upon which corrections (offset) are made over time
when FT.CF = Yes. It is the constant control point for delta cfm
control when FT.CF = No.
Fan Track Minimum Clamp (FT.MN)
For BP.CF = 5, this return/exhaust control configuration is the
minimum positive delta cfm control value allowed unless outdoor
air cfm control is available and then the delta cfm control value
would be clamped to the outdoor air cfm value directly (see the
Economizer section on page 75 for a description of outdoor air
cfm configuration).
Fan Track Max Clamp (FT.MX)
For BP.CF = 5, this return/exhaust control configuration is the
maximum positive delta cfm control value allowed unless outdoor
84
CCN POINT
DEFAULT
BLDG_CFG
0
a
BPSENS
Disable
a
BP_RANGE
0.25
BPSP
0.05
BPSO
0.05
PES1
25
PES2
75
BLDGPFSO
100
BLDGPMIN
10
BLDGPMAX
100
BP1SETMX
100
BP2SETMX
100
BLDGCLMP
10
DCFM_CFG
No
DCFMRATE
15
DCFMSTRT
2000
DCFM_MAX
4000
DCFM_MIN
–1000
DCFM_ADJ
1000
DCFM_OFF
0
DCFM_RAM
0
DCFMRSET
No
SCFM_CFG
1
BPIDRATE
10
BLDGP_PG
0.5
BLDGP_IG
0.5
BLDGP_DG
0.3
BP_1_SN1
0
BP_1_SN2
0
BP_1_SN3
0
BP_1_SN4
0
BP1_CALM
35
BP_2_SN1
0
BP_2_SN2
0
BP_2_SN3
0
BP_2_SN4
0
BP2_CALM
35