Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 152

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

BOARD NO.
TERMINAL NO.
TB-1 - POWER CONNECTION OR DISCONNECT (in Main Control Box)
11
TB1
12
13
NEUTRAL (in Main Control Box)
Neutral
1
TB201 - FIELD CONNECTIONS (in Main Control Box)
1
2
3
4
5
6
7
8
9
10
R
Y1
Y2
W1
W2
TB201
G
C
X
FS1
FS2
T55-1
T55-2
T55-3
HUM1
HUM2
(+)
(COM)
(-)
SHIELD
LEN
CCN
TB202 - FIELD CONNECTIONS CEM (in Main Control Box)
1
2
3
4
5
6
7
8
9
10
11
12
TB202
13
14
15
16
17
18
19
20
21
22
23
24
25
LEGEND
IAQ — Indoor Air Quality
VAV — Variable Air Volume
Table 114 — Field Terminal Connections
DESCRIPTION
L1 power supply
L2 power supply
L3 power supply
Neutral Power
Smoke Detector Alarm Input
Smoke Detector Alarm Input
Remote Occupied/Economizer Enable 24 vac out
Remote Occupied/Economizer Enable 24 vac in
Outdoor Enthalpy Switch 24 vac out
Outdoor Enthalpy Switch 24 vac in
Indoor Air IAQ Remote Sensor/Remote 
Pot/Remote 4-20 mA
Indoor Air IAQ Remote Sensor/Remote 
Pot/Remote 4-20 mA
VAV Heater Interlock Relay
VAV Heater Interlock Relay
24 vac Power
Thermostat Y1 (1st stage cool)
Thermostat Y2 (2nd stage cool)
Thermostat W1 (1st stage heat)
Thermostat W2 (2nd stage heat)
Thermostat G (Fan)
24 vac Common
Alarm Output (NO)
Fire Shut Down
Fire Shut Down
Space Sensor TH
Space Sensor COM
Space Sensor Offset Switch
Humidifier Output
Humidifier Output
CCN +
CCN Common
CCN -
Ground
Local Equipment Network
Carrier Comfort Network
Not Used
Not Used
Space Humidity 4-20 mA (-)
Space Humidity 4-20 mA (+)
Ground
Outdoor Air IAQ 4-20 mA (-)
Outdoor Air IAQ 4-20 mA (+)
Supply Air Reset 4-20 mA (-)
Supply Air Reset 4-20 mA (+)
Demand Limit 4-20 mA (-)
Demand Limit 4-20 mA (+)
IAQ Switch 24 vac in
IAQ Switch 24 vac out
Fire Smoke Purge 24 vac in
Fire Smoke Purge 24 vac out
Fire Evacuation 24 vac in
Fire Evacuation 24 vac out
Fire Pressurization 24 vac in
Fire Pressurization 24 vac out
Demand Limit Loadshed 24 vac in
Demand Limit Loadshed 24 vac out
Demand Limit Redline 24 vac in
Demand Limit Redline 24 vac out
Humidistat
Humidistat
208-230/460/575/380/-3-60, 400-3-50
208-230/460/575/380/-3-60, 400-3-50
208-230/460/575/380/-3-60, 400-3-50
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
24 vac Output
24 vac Input
24 vac Output
24 vac Input
Thermistor input or externally powered 4 to 20 mA when used with 
180 ohm resistor
Thermistor input or externally powered 4 to 20 mA when used with 
180 ohm resistor
Contact (maximum 24 vac, 3 A)
Contact (maximum 24 vac, 3 A)
24 vac Output
24 vac Input
24 vac Input
24 vac Input
24 vac Input
24 vac Input
24 vac Output
24 vac Output
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
Thermistor Input
Thermistor Input
Thermistor Input
Contact (maximum 24 vac, 3 A)
Contact (maximum 24 vac, 3 A)
Communication
Communication
Communication
Ground
Communication
Communication
4 to 20 mA signal
4 to 20 mA loop power
Ground
4 to 20 mA signal
4 to 20 mA loop power
4 to 20 mA signal
4 to 20 mA loop power
4 to 20 mA signal
4 to 20 mA loop power
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
152
TYPE