ITEM
EXPANSION
TEST
Test Display LEDs
METR
Metric Display
LANG
Language Selection
PAS.E
Password Enable
PASS
Service Password
ITEM
EXPANSION
S.VFD
SUPPLY FAN VFD CONFIG
N.VLT
VFD1 Nominal Motor Volts
N.AMP
VFD1 Nominal Motor Amps
N.FRQ
VFD1 Nominal Motor Freq
N.RPM
VFD1 Nominal Motor rpm
N.PWR
VFD1 Nominal Motor HPwr
M.DIR
VFD1 Motor Direction
ACCL
VFD1 Acceleration Time
DECL
VFD1 Deceleration Time
SW.FQ
VFD1 Switching Frequency
TYPE
VFD1 Type
NOTE(S):
a. This default is model number dependent.
ITEM
EXPANSION
E.VFD
EXHAUST FAN VFD CONFIG
N.VLT
VFD2 Nominal Motor Volts
N.AMP
VFD2 Nominal Motor Amps
N.FRQ
VFD2 Nominal Motor Freq
N.RPM
VFD2 Nominal Motor rpm
N.PWR
VFD2 Nominal Motor HPwr
M.DIR
VFD2 Motor Direction
ACCL
VFD2 Acceleration Time
DECL
VFD2 Deceleration Time
SW.FQ
VFD2 Switching Frequency
TYPE
VFD2 Type
NOTE(S):
a. This default is model number dependent.
EXHAUST FAN VFD CONFIGURATION
The sub-menu that contains these configurations is located at the
local display under Configuration
VFD2 Nominal Motor Volts (N.VLT)
This configuration defines the nominal motor voltage. This val-
ue must equal the value on the motor rating plate. This value sets
the maximum drive output voltage supplied to the motor.
NOTE: The VFD cannot supply the motor with a voltage greater
than the voltage supplied to the VFD input. Power to the VFD must
be cycled for a change to this configuration to take effect.
VFD2 Nominal Motor Amps (N.AMP)
This configuration defines the nominal motor current. This value
must equal the value defined in:
the High-Capacity Power Exhaust Systems Motor Limita-
tions table (Table 29) if BP.CF=4
the Supply Fan Motor Limitations table (Table 27) if
BP.CF=5
the Optional VFD Power Exhaust Motor Limitations table
(Table 82) if BP.CF=3
Power to the VFD must be cycled in order for a change to this
configuration to take effect.
Table 79 — Display Configuration
ON/OFF
ON/OFF
0-1(multi-text strings)
ENABLE/DISABLE
0000-9999
Table 80 — Supply Fan VFD Configuration
0 to 999
0 to 999
10 to 500
50 to 30000
0 to 500
0=FWD, 1=REV
0 to 1800
0 to 1800
0=1kHz, 1=4kHz, 2=8kHz, 3=12kHz
0=LEN, 1=ANALOG
Table 81 — Exhaust Fan VFD Configuration
0 to 999
0 to 999
10 to 500
50 to 30000
0 to 500
0=FWD, 1=REV
0 to 1800
0 to 1800
0=1kHz, 1=4kHz, 2=8kHz, 3=12kHz
0=LEN, 1=ANALOG
E.VFD.
RANGE
RANGE
RANGE
Table 82 — Optional VFD Power Exhaust (PE) Motor
Limitations (FLA)
Power
Exhaust HP
208/230
6
20.4
10
30.6
15
44.8
20
58.6
Premium Efficiency PE
6
16.0
10
29.4
15
43.0
20
56.0
VFD2 Nominal Motor Freq (N.FRQ)
This configuration defines the nominal motor frequency. This val-
ue must equal the value on the motor rating plate. This value sets
the frequency at which the output voltage equals the Nominal
Motor Volts (N.VLT). Power to the VFD must be cycled in order
for a change to this configuration to take effect.
VFD2 Nominal Motor rpm (N.RPM)
This configuration defines the nominal motor speed. This value
must equal the value on the motor rating plate. Power to the VFD
must be cycled for a change to this configuration to take effect.
102
UNITS
CCN POINT
TEST
Off
DISPUNIT
Off
LANGUAGE
0
PASS_EBL
Enable
PASSWORD
1111
UNITS
CCN POINT
Volts
VFD1NVLT
460
Amps
VFD1NAMP
55.0
Hz
VFD1NFRQ
60
rpm
VFD1Nrpm
1750
HP
VFD1NPWR
40
VFD1MDIR
0
sec
VFD1ACCL
30
sec
VFD1DECL
30
VFD1SWFQ
2
VFD1TYPE
0
UNITS
CCN POINT
Volts
VFD2NVLT
460
Amps
VFD2NAMP
28.7
Hz
VFD2NFRQ
60
rpm
VFD2Nrpm
1750
H.P.
VFD2NPWR
20
VFD2MDIR
0
sec
VFD2ACCL
30
sec
VFD2DECL
30
VFD2SWFQ
2
VFD2TYPE
0
UNIT VOLTAGE
380
460
High Efficiency PE
10.0
9.6
18.2
12.8
24.4
19.4
32.4
26.8
8.0
13.6
19.4
25.2
DEFAULT
DEFAULT
a
a
a
DEFAULT
a
a
a
575
7.6
10.2
15.6
20.6