Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 164

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

150
145
140
135
130
125
120
115
110
105
100
95
90
85
55
60
65
Fig. 56 — Charging Chart — 48/50P030 Standard Units — Circuit A
150
145
140
135
130
Reduce Charge if Above Curve
125
120
115
110
105
100
95
90
85
55
60
65
70
Fig. 57 — Charging Chart — 48/50P030 Standard Units — Circuit B
30 Ton STD CAP CIRCUIT A Charging Chart
All Compressors on a Circuit Must Be Operating
All Outdoor Fans Must Be Operating
Reduce Charge if Above Curve
70
75
80
85
Outdoor Air Temperature (deg F)
30 Ton STD CAP CIRCUIT B Charging Chart
All Compressors on a Circuit Must
Be
All Outdoor Fans Must
Operating
75
80
85
90
Outdoor Air Temperature (deg F)
164
Add Charge if Below Curve
90
95
100
105
Be
Operating
Add Charge if Below Curve
95
100
105
a48-8518
SST= 60 F
SST= 45 F
SST= 30 F
110
115
120
a48-8519
SST= 60 F
SST= 45 F
SST= 30 F
110
115
120