Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 220

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

Table Y — VAV and Adaptive CV Staging Sequence (Sizes 090-100)
STAGE
0
COMP
A1
OFF
A2
OFF
A3
OFF
B1
OFF
B2
OFF
B3
OFF
UNIT
090
0%
100
0%
NOTE(S):
a. Minimum load valve.
Table Z — VAV (with Digital Compressor) Staging Sequence (Sizes 090-100)
STAGE
0
COMP
A1
OFF
a
A2
OFF
A3
OFF
B1
OFF
B2
OFF
B3
OFF
UNIT
090
0%
100
0%
NOTE(S):
a. On units with optional digital scroll compressor, compressor A1 modulates from minimum to maximum capacity to provide increased stages.
APPENDIX C — UNIT STAGING TABLES (CONT)
1
a
1
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
12%
17%
11%
15%
1
2
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
8% to 17%
25% to 33%
8% to 15%
26% to 33%
SEQUENCE
2
3
Compressor Status
ON
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
Capacity 48/50P
33%
50%
33%
49%
SEQUENCE
3
4
Compressor Status
ON
ON
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
Capacity 48/50P
42% to 50%
58% to 67%
41% to 49%
59% to 67%
220
4
5
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
OFF
OFF
67%
83%
67%
82%
5
ON
ON
ON
ON
ON
OFF
75% to 83%
92% to 100%
74% to 82%
92% to 100%
6
ON
ON
ON
ON
ON
ON
100%
100%
6
ON
ON
ON
ON
ON
ON