Mitsubishi Electric MELSEC iQ-FX5 User Manual page 239

Application
Table of Contents

Advertisement

Setting method from the CPU module
The following shows the data settings and program example for changing the control speed of axis 1 by the command from
the CPU module. (In this example, the control speed is changed to "20.00 mm/min".)
• Set the following data.
(Set using the program referring to the speed change time chart.)
n: Axis No. - 1
Setting item
[Cd.14]
New speed value
[Cd.15]
Speed change request
Refer to the following for the setting details.
Page 470 Control Data
• The following shows the speed change time chart.
■Operation example
V
[Cd.184] Positioning start signal
[Cd.190] PLC READY signal
[Cd.191] All axis servo ON signal
READY signal
([Md.140] Module status: b0)
Start complete signal
([Md.31] Status: b14)
[Md.141] BUSY signal
Positioning complete signal
([Md.31] Status: b15)
Error detection signal
([Md.31] Status: b13)
[Md.40] In speed change
processing flag
[Cd.14] New speed value
[Cd.15] Speed change request
Program example
Refer to the following for the program example of the speed change program.
Page 535 Speed change program
Setting value
Setting details
2000
Set the new speed.
1
Set "1: Change the speed".
0
1
0
1
Buffer memory address
4314+100n
4315+100n
4316+100n
Dwell time
0
2000
0
7 CONTROL SUB FUNCTIONS
7.5 Functions to Change the Control Details
t
7
237