5.8.3. Connect the Interlock cable for the HVC 150 kW system

Interlock cable connection in the primary HVC 150:
A
Terminal block
B
Interlock cable from/to ACS Control Module (ACM)
1.
Move the cable towards the terminal block (A).
2.
Strip 0.43 Inch of the insulation from the ends of only the White and Brown wire!
3.
Crimp a ferrule onto the end of the White and Brown wire.
4.
Ensure that the unused wires, the Green and Yellow wire, are protected so that they
cannot touch metal parts.
5.
Make a wire connection between pin X286-6 and X286-7 and pin X286-10 and X286-11.
6.
Loosen the connector screws.
7.
Insert the wires into the connectors, see table below:
Functional description
Interlock In
Interlock Out
Interlock GND
Interlock loop
Interlock loop
Interlock loop
Interlock loop
See also Appendix H Signal connection diagram.
8.
Tighten the connector screws with a tightening torque of 1.0 ft-lb.
Document: V1.2 / Document No.: 6AGA000008-0629-EN | Date: 06-30-2022
HVC‐PD E‐Bus Charger Installation Guide 
Connector
Wire number
X286-15
Brown
X286-14
White
X286
Shield
X286-6
Black
X286-7
Black
X286-10
Black
X286-11
Black
Page 77 of 146