CHAPTER 2 WIRING
 Parameter setting
To assign the command position completion to IQ area (sequence output terminal), specify the
corresponding value ("82") to the output terminal function setting parameter.
2

CONTa Through: Sequence output signal (Reference value 91)

CONTb Through: Sequence output signal (Reference value 92)

The signals input to IQ area on the SX controller side can be output to the OUT signal of the servo
amplifier. The general-purpose output of 2 bits is enabled.
This is used as a sequence output signal when output signals are insufficient or in a similar case.
This signal is enabled only for VS type.
 Function
When the CONTa Through (reference value 91) is assigned to OUT1 signal assignment, the
relation of signal logic is as follows.
CONT a(CONT6)
0:FALSE
1:TRUE
The signal status of CONT6 (%QX*.15.6) is send with through output to OUT1 regardless of the
CONT6 signal assignment.
The output signal is turned off in the following cases.
 The SX bus has not been established.
 The SX bus base board power is turned off, the cable is disconnected.
 The program is stopped by D300win.
Amplifier→PLC
PLC→Amplifier
2-110
Description of I/O Signals
OUT1
OFF
ON
APS 30
ONL
1
ONL 0 1 2 3 4 5 6 7
ONL 0 1 2 3 4 5 6 7
EMG + OT - OT
ERR 8 9 101112131415
ERR 8 9 101112131415
ERR
2
PW
AL
20
CH
CH
R
M
1
B / A
MP 2 C
2 C
1
IQ area
H
H
Address+15
bit6:CONT6
bit5:CONT7
OUT1,2
output