CHAPTER 4 PARAMETER

PA3_26 to 30 CONT always ON 1 to 5

No.
26
CONT always ON 1
27
CONT always ON 2
28
CONT always ON 3
29
CONT always ON 4
30
CONT always ON 5
Specify the CONT input signal that is always enabled after the power is turned on.
The normally open contact signal is always turned on. The normally closed contact signal is always
4
turned off.
Functions that may not be specified with a normally open signal include alarm reset, deviation clear
and free-run.
Functions that may not be specified with a normally closed signal include forced stop and external
braking resistor overheat. (Functions that can be specified with a normally closed signal are +OT
and -OT.)
For example, to turn forward command [FWD] always on, specify "2," which corresponds to the
forward command, to one of CONT always ON signals 1 to 5.
The signal assigned to CONT input signal can be also assigned to CONT always enabled setting
redundantly.

PA3_36 Deviation clear input form

No.
Deviation clear input
36
form
Specify the deviation clear input signal format.
Select 0 (edge) to reset position deviation at the rising edge timing.
4-100
Input Terminal Function Setting Parameters
Name
Specify the number corresponding to
desired function (0 to 76)
Name
0: Edge 1: Level
Setting range
Setting range
Default
Change
value
0
Power
Change
Default value
0
Power