Monitor Mode

Q9 Plus ASD Install/Op Manual
Monitor Mode
The Monitor mode allows the user to monitor motor
performance variables, control settings, and
configuration data during motor operation. The
items are listed and described below.
Press the Rotary Encoder to access the listing of
monitored parameters. Turn the Rotary Encoder to
access subsequent monitored parameters.
Note:
The Monitor mode is a read-only
mode. The settings cannot be
changed from the Monitor mode.
For information on how to change
the values, see the section titled
Monitored
Default Setting Changes on pg. 29
Items
Note: Any two of the Underlined monitored items
may be selected for display at the Frequency
Command screen while running via Program
Utilities

Note:
The
the Current and Voltage values
displayed appear as A (Amps) or V
(Voltage), or if the value is shown
as a % (Percentage) of the ASD
rating.
Frequency at Trip — Displays the at-trip
frequency.
Frequency Reference — Displays the Frequency
Setpoint (commanded frequency).
Output Current — Displays the Output Current as
a percentage of the rated capacity of the ASD.
DC Voltage — Displays the DC Bus Voltage as a
percentage of the rated capacity of the ASD.
Output Voltage — Displays the Output Voltage as
a percentage of the rated capacity of the ASD.
AM Output — Displays the magnitude of the
function assigned to this terminal relative to the full-
scale reading of the AM terminal. This terminal may
be configured at
suitability.
FM Output — Displays the magnitude of the
function assigned to this terminal relative to the full-
scale reading of the FM terminal. This terminal may
be configured at
suitability.
38
Main Monitor Selections.
F701
setting will determine if
F670
for application-specific
for application-specific
F005
Motor OL (Overload) Real — Displays the real-
time Motor Overload value as a percentage of the
rated capacity of the motor.
Motor OL (Overload) Trip — Displays the Motor
Overload Trip value as a percentage of the rated
capacity of the motor.
Motor Load — Displays the real-time Motor Load
as a percentage of the rated capacity of the motor.
ASD OL (Overload) Real — Displays the real-time
ASD Overload as a percentage of the rated
capacity of the ASD.
ASD OL (Overload) Trip — Displays the ASD
Overload Trip value as a percentage of the rated
capacity of the ASD.
.
ASD Load — Displays the ASD Load as a
percentage of the rated capacity of the ASD.
Run Time — Displays the Cumulative Run Time in
hours. Select Clear Run Timer at
reading.
Compensation Frequency — Displays the Output
Frequency after the application of the slip
compensation correction value (post compensation
frequency).
DBR OL (Overload) Real (not used) — Displays
the real-time DBR Overload value as a percentage
of the Dynamic Braking Resistor capacity.
DBR OL (Overload) Trip (not used) — Displays
the DBR Overload Trip value as a percentage of the
Dynamic Braking Resistor capacity.
DBR Load (not used) — Displays the DBR Load
as a percentage of the Dynamic Braking Resistor
capacity.
Feedback (Inst) — Provides a status of the Real-
Time Feedback in Hz.
Feedback (1 Second) — Provides a status of the
1-Second Averaging feedback in Hz.
Torque — Displays the Output Torque as a
percentage of the rated capacity of the Q9 Plus
ASD.
Torque Reference — Displays the Torque
Reference as a percentage of the maximum torque
available.
Torque Current — Displays the torque-producing
current value.
Exciting Current — Displays the current value
required to produce the excitation field.