Toshiba Q9+ Installation & Operation Manual page 122

Adjustable speed drives
Table of Contents

Advertisement

RR Input Point 1 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input
terminal when the RR terminal is used as the control input while
operating in the Speed Control mode.
This parameter sets RR Input Point 1 Frequency and is the fre-
quency that is associated with the setting of RR Input Point 1 Set-
ting when operating in the Speed Control mode.
See RR Input Point 1 Setting (F210) for additional information on
this parameter.
RR Input Point 2 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input
terminal when the RR terminal is used as the control input while
operating in the Speed Control mode or the Torque Control
mode.
This parameter sets the RR input level that is associated with RR
Input Point 2 Frequency when operating in the Speed control
mode or is associated with the RR Input Point 1 Rate when oper-
ating in the Torque Control mode.
This value is entered as 0% to 100% of the RR input signal
range.
See RR Input Point 1 Setting (F210) for additional information on
this parameter when used for Speed control.
See RR Input Point 1 Rate (F214) for additional information on
this parameter when used for Torque Control.
RR Input Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input
terminal when the RR terminal is used as the control input while
operating in the Speed Control mode.
This parameter sets RR Input Point 2 Frequency and is the fre-
quency that is associated with the setting of RR Input Point 2 Set-
ting when operating in the Speed Control mode.
See RR Input Point 1 Setting (F210) for additional information on
this parameter.
110
F211
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F214
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
Direct Access Number —
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
https://www.toshiba.com/tic/
F211
F212