This setting determines the output function of the FM analog out-
put terminal. The FM output terminal produces an output voltage
or current that is proportional to the magnitude of the function
assigned to this terminal. Select the terminal output signal type at
F681
(i.e., current or voltage).
The available assignments for this output terminal are listed in
Table 10 on page
255.
Note: If the monitored item has a positive and a negative
component, use the Expansion I/O Card 2 (P/N ETB004Z).
See the Expansion IO Card Option 2 instruction manual
(P/N 58686) for additional information on the functions of
the option card.
See
F678
and
F684
for additional information on this parameter.
To read Voltage at this terminal, configure the meter to read DC
voltage, and connect the leads of the meter to FM (+) and
CCA (-).
To read Current at this terminal, configure the meter to read DC
current, and connect the leads of the meter to FM (+) and
CCA (-).
FM Terminal Setup Parameters
F005
— Set FM Function
F006
— Calibrate FM Terminal
F681
— Voltage/Current Output Switching Selection
F682
— Output Response Polarity Selection
F683
— Set Zero Level
https://www.toshiba.com/tic/
F005
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F006
Direct Access Number —
Parameter Type — Selection List
Factory Default — Output Fre-
quency
Changeable During Run — Yes
F005
75