AM Output Terminal Adjustment
Program Terminal Analog Output Terminals
This parameter is used to calibrate the AM analog output.
To calibrate the AM analog output, connect an ammeter as
described at parameter F670.
While the ASD is running at a known value (e.g., output fre-
quency), adjust this parameter until the associated function of
parameter
F670
produces the desired DC level output at the AM
output terminal.
See
F670
for additional information on this parameter.
MON1 Terminal Meter Selection
Program Terminal Analog Output Terminals
This parameter is used to set the output function of the MON1
analog output terminal. The available assignments for this output
terminal are listed in
Table 10 on page
The MON1 analog output terminal produces an output voltage or
current that is proportional to the magnitude of the function
assigned to this terminal.
Note: The Expansion IO Card Option 2 option board (P/N
ETB004Z) is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N
58686) for additional information on the function of this terminal.
MON1 Terminal Setup Parameters
F672
— MON1 Output Function
F673
— MON1 Terminal Meter Adjustment
F688
— MON1 Voltage/Current Output Switching
F689
— MON1 Output Gradient Characteristic
F690
— MON1 Bias Adjustment Set Zero Level
MON1 Terminal Meter Adjustment
Program Terminal Analog Output Terminals
This parameter is used to set the gain of the MON1 output termi-
nal and is used in conjunction with the settings of parameter
F672.
See
F672
for additional information on this parameter.
https://www.toshiba.com/tic/
F671
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
255.
F674
Direct Access Number —
Parameter Type — Numerical
Factory Default — 154
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number —
Parameter Type — Selection List
Factory Default — Output Voltage
Changeable During Run — Yes
Direct Access Number —
Parameter Type — Numerical
Factory Default — 682
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
F671
F672
F673