PG Input Point 1 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the PG input
terminal of the option board when a shaft-mounted encoder is
used as the control input while operating in the Speed Control
mode.
Note: See Instruction Manual P/N 58687 for additional
information on the PG Option Board.
PG Input Speed Control Setup
Perform the following setup to allow the system to receive Speed
control input at the PG input terminal:
• Program Fundamental Standard Mode Selection
Frequency Mode 1 Pulse Input (option).
• Program Fundamental Standard Mode Selection
Command Mode Selection (any setting).
• Provide a Run command (F and/or R).
Speed Control
Perform the following setup to allow the system to perform Speed
control from the PG input terminals:
• Set PG Point 1 Frequency (F235).
• Set the PG input value (F234) that represents PG Point 1
Frequency.
• Set PG Point 2 Frequency (F237).
• Set the PG input value (F236) that represents PG Point 2
Frequency.
Once set, as the PG input pulse count rate changes, the output
frequency of the ASD will vary in accordance with the above set-
tings.
This parameter sets the PG input pulse count that represents
Reference Setpoint 1 (frequency). The range of values for this
parameter is 0% to 100% of the PG input pulse count range.
Note: Further application-specific PG settings may be performed
from the following path: Program Feedback PG
Settings
https://www.toshiba.com/tic/
–
F234
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F235
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Frequency Settings
F234
121