Toshiba Q9+ Installation & Operation Manual page 97

Adjustable speed drives
Table of Contents

Advertisement

Low-Speed Signal Output Frequency
Program Terminal Reach Settings
The Low-Speed Signal Output Frequency parameter sets an
ASD output frequency threshold that activates the assigned dis-
crete output terminal for the duration that the ASD output speed
is equal to or less than this setting.
Speed Reach Frequency
Program Terminal Reach Settings
The Speed Reach Frequency sets a frequency threshold that,
when reached or is within the bandwidth specified by parameter
F102, activates the assigned discrete output terminal for the
duration that the ASD output is within the
Speed Reach Detection Band
Program Terminal  Reach Settings
This parameter sets the bandwidth of the Speed Reach Fre-
quency
(F101)
setting.
Forward/Reverse Run Priority When Both Are Closed
Program Terminal Input Special Functions
The Forward/Reverse Priority Selection determines the operation
of the ASD if the F and R control terminals are activated simulta-
neously.
Settings:
0 — Reverse
1 — Suspend
The waveforms shown depict the motor response for all combina-
tions of the F and R terminal settings if the Reverse option is cho-
sen.
The Suspend setting will decelerate the motor to a stop regard-
less of the rotation direction when both the F and R control termi-
nals are activated.
https://www.toshiba.com/tic/
F100
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F102
bandwidth.
F106
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
Direct Access Number —
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
Direct Access Number —
Parameter Type — Selection List
Factory Default — Suspend
Changeable During Run — No
Simultaneous F and R activation.
F100
F101
F102
F105
85