BIN Input Point 1 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the BIN input
terminals when the BIN terminals are used as the control input
while operating in the Speed Control mode.
The discrete input terminals of the Terminal Board are used as
the BIN terminals.
BIN Input Speed Control Setup
Perform the following setup to allow the system to receive Speed
control input at the BIN input terminals:
• Program Fundamental Standard Mode Selection 
Frequency Mode 1 Binary/BCD.
• Program Fundamental Standard Mode Selection 
Command Mode Selection Terminal Board.
• Program Terminal Input Terminals; select and set the
desired discrete input terminals to Binary Bit(s) 0 – 7 (or 0 –
MSB). The binary input byte will control the speed of the
motor.
• Program Terminal Input Terminals; select and set a
discrete input terminal to Binary Data Write. Activation of the
Binary Data Write terminal will transfer the status of the Binary
Bit(s) 0 – 7 (or 0 – MSB) to the control board for speed control.
Speed Control
Perform the following setup to allow the system to perform Speed
control from the BIN input terminals:
• Set BIN Input Point 1 Frequency (F229).
• Set the BIN input value (% of 255
BIN Input Point 1 Frequency.
• Set BIN Input Point 2 Frequency (F231).
• Set the BIN input value (% of 255
BIN Input Point 2 Frequency.
• Provide a Run command (F and/or R).
Note: 255
is the decimal equivalent of the 8-bit BIN byte with all
D
input terminals set to 1 (255 decimal = 11111111 binary).
Once set, as the BIN input signal changes are transferred to the
control board, the output frequency of the ASD will vary in accor-
dance with the above settings.
This parameter sets BIN Input Point 1 Setting and is entered as
0% to 100% of the range represented by the BIN binary input
byte 11111111 (255
) or the binary bit(s) 0 – MSB.
D
https://www.toshiba.com/tic/
F228
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
) (F228) that represents
D
) (F230) that represents
D
F229
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %