V/f 5-Point Setting Voltage 1
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 1 setting establishes the output
voltage level that is to be associated with the frequency setting of
F190
(V/f 5-Point Setting Frequency 1).
The
F701
parameter setting will determine if the on-screen selec-
tion for this parameter appears in the form of a Voltage (V) or as
a Percentage (%) of the ASD rating.
If using Voltage as a unit of measure and with no voltage correc-
tion
(F307
Disabled), the limit of the on-screen display value for
this parameter is 200 volts for the 230-volt ASD and 400 volts for
the 460-volt ASD.
The actual output voltage is scaled to the maximum EOI display
values (e.g., a 100-volt EOI display corresponds to a 115-volt
actual output for the 230-volt ASD — ½ of the full display range).
If using % as a unit of measure and with no voltage correction
(F307
Disabled), the ASD output voltage will be the percentage
setting times 230 for the 230-volt unit (or % times 460 volts for
the 460-volt unit).
See
F190
for additional information on this parameter.
V/f 5-Point Setting Frequency 2
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 2 sets the frequency to be
associated with the voltage setting of parameter
Setting Voltage 2).
See
F190
and
F191
for additional information on this parameter.
100
F191
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F193
F193
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
(V/f 5-Point
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz