My Function Percent Data 3
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the
analog signal of the My Function Percent Data 3.
The analog signal is selected using the Input Setting number
from
Table 12 on page
257.
My Function Percent Data 4
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the
analog signal of the My Function Percent Data 4.
The analog signal is selected using the Input Setting number
from
Table 12 on page
257.
My Function Percent Data 5
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the
analog signal of the My Function Percent Data 5.
The analog signal is selected using the Input Setting number
from
Table 12 on page
257.
My Function Frequency Data 1
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the
analog signal of the My Function Frequency Data 1.
The analog signal is selected using the Input Setting number
from
Table 12 on page
257.
My Function Frequency Data 2
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the
analog signal of the My Function Frequency Data 2.
The analog signal is selected using the Input Setting number
from
Table 12 on page
257.
https://www.toshiba.com/tic/
F920
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F925
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.00
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.00
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.00
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — %
F920
F921
F922
F923
F924
233