MON1 Voltage/Current Output Switching
Program Terminal Analog Output Terminals
This parameter is used to set the output signal type of the MON1
output terminal.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
MON1 Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the MON1
output terminal. The MON1 output terminal response may be set
to respond inversely (-) or directly (+) to the input signal.
See
F672
for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
MON1 Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input
signal produces a zero-level output at the MON1 terminal.
Set the assigned function of parameter
this parameter to a zero output.
See
F672
for additional information on this parameter.
MON2 Voltage/Current Output Switching
Program Terminal Analog Output Terminals
This parameter is used to set the output signal type of the MON2
output terminal.
See
F674
for additional information on this parameter.
Settings:
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
204
–
F688
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F672
to zero and then set
F692
Direct Access Number —
Parameter Type — Selection List
Factory Default — 0 – 10 V
Changeable During Run — No
Direct Access Number —
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %
Direct Access Number —
Parameter Type — Selection List
Factory Default — 0 – 10V
Changeable During Run — No