RX2 Input Point 1 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX2 input
terminal when the RX2 terminal is used as the control input while
operating in the Speed Control mode or the Torque Control
mode.
Note: The Expansion IO Card Option 1 option board (P/N
ETB003Z) is required to use this terminal.
This parameter sets the RX2 input level that is associated with
RX2 Input Point 1 Frequency when operating in the Speed Con-
trol mode or is associated with the RX2 Input Point 1 Rate when
operating in the Torque Control mode.
RX2 Input Speed Control Setup
Perform the following setup to allow the system to receive Speed
control input at the RX2 input terminal:
• Program Fundamental Standard Mode Selection 
Frequency Mode 1 RX2.
• Program Fundamental Standard Mode Selection 
Command Mode Selection Terminal Board.
Speed Control
Perform the following setup to allow the system to perform Speed
control from the RX2 input terminal:
• Set RX2 Input Point 1 Frequency (F223).
• Set RX2 Input Point 1 Setting (F222) — the input analog
signal level that corresponds to the speed setting at RX2 Input
Point 1 Frequency.
• Set RX2 Input Point 2 Frequency (F225).
• Set RX2 Input Point 2 Setting (F224) — the input analog
signal level that corresponds to the speed setting at RX Input
Point 2 Frequency.
• Provide a Run command (F and/or R).
Once set, as the RX2 input voltage changes, the ASD output
speed and/or torque will vary in accordance with the above set-
tings.
This parameter value is entered as -100% to +100% of the RX2
input signal range.
See the Expansion IO Card Option 1 instruction manual (P/N
58685) for additional information on the function of this terminal.
See
F476
and
F477
for information on fine-tuning this terminal
response.
https://www.toshiba.com/tic/
F222
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F223
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — -100
Maximum — +100
Units — %