Power Running Torque Limit 1
Program Torque Torque Limit Settings
This parameter determines the source of the control signal for the
positive torque limit setting.
If
F441
is selected, the value set at
Running Torque Limit 1 input.
Settings:
1 — V/I
2 — RR
3 — RX
4 —
F441
(Setting)
Power Running Torque Limit 1 Level
Program Torque Torque Limit Settings
This parameter provides a value for the Power Running Torque
Limit 1 setting if
F441
is selected at parameter F440.
This value provides the positive torque upper limit for the 1 motor.
Regenerative Braking Torque Limit 1
Program Torque Torque Limit Settings
This parameter determines the source of the Regenerative
Torque Limit control signal.
If
F443
is selected, the value set at
ative Torque Limit setting.
Settings:
1 — V/I
2 — RR
3 — RX
4 —
F443
(Setting)
Regenerative Braking Torque Limit 1 Level
Program Torque Torque Limit Settings
This parameter provides a value to be used as the Regeneration
Torque Limit 1 if
F443
is selected at parameter F442.
Set this parameter to 250% to disable this function.
https://www.toshiba.com/tic/
–
F440
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F441
is used as the Power
F443
is used as the Regener-
F450
Direct Access Number —
Parameter Type — Selection List
Factory Default
Changeable During Run — Yes
Direct Access Number —
Parameter Type — Numerical
Factory Default — 250.00 (Dis-
abled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00 (Disabled)
Units — %
Direct Access Number —
Parameter Type — Selection List
Factory Default —
Changeable During Run — Yes
Direct Access Number —
Parameter Type — Numerical
Factory Default — 250.0 (Dis-
abled)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 250.0
Units — %
F440
—F441
(Setting)
F441
F442
F443
Setting
F443
163