The Q9 Plus ASD has the ability to allow the user direct access to the motor control functions. There
are two ways in which the motor control parameters may be accessed for modification from the EOI:
Program  Applicable Menu Path or Program  Direct Access  Applicable Parameter Number .Both
methods access the parameter via the Program mode. Parameters may also be accessed via
communications. Once accessed, the parameter may be viewed or changed.
The Program mode allows the user to develop an application-specific motor control profile. Motor
control functions may be set to accommodate specific power and timing requirements for a given
application. The configurable parameters of the Program mode that have user-accessible Parameter
Numbers are listed and described below.
Note: Parameter Settings are preceded by the number used to select an item if using communications
to write to a parameter location in memory (i.e., F000  0-Manual, 1- Automatic ACC/DEC, 2--
Automatic ACC Only, etc.).
Note: Communications setting changes will require that the ASD input power be removed and then re-
applied for the changes to take affect.
Direct Access Parameters/Numbers
Automatic Acceleration/Deceleration
Program  Fundamental Accel/Decel 1 Settings
This parameter is used to enable acceleration and deceleration
rates in accordance with the applied load automatically.
The adjusted acceleration and deceleration times range from
12.5% to 800% of the programmed values for Acceleration Time
1 (F009) and Deceleration Time 1 (F010).
Settings:
0 — Manual
1 — Automatic ACC/DEC
2 — Automatic ACC Only
Note: The motor and the load must be connected prior to
selecting Automatic Acceleration/Deceleration.
Automatic Torque Boost
Program  Fundamental Motor Set 1
This parameter allows the ASD to adjust the output torque in
accordance with the applied load automatically. When enabled,
Autotuning is performed (the motor should be connected before
performing an Autotune).
Note: If selecting 1 or 2, the motor must be connected or the
Autotune results will not be valid.
Settings:
0 — Disabled
1 — Automatic Torque Boost + Autotuning
2 — Sensorless Vector Control (Speed) + Autotuning
https://www.toshiba.com/tic/
F000
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F003
Direct Access Number —
Parameter Type — Selection List
Factory Default — Manual
Changeable During Run — No
Direct Access Number —
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
F000