Toshiba Q9+ Installation & Operation Manual page 81

Adjustable speed drives
Table of Contents

Advertisement

Binary Value
Object Name
Object ID
Binary Value
Drive Ready
#7 (BV7)
Binary Value
At Set-Point
#8 (BV8)
Binary Value
Run/Stop
#10 (BV10)
Cmd
Binary Value
Fwd/Rev Cmd
#11 (BV11)
Binary Value
Fault Reset
#14 (BV14)
Binary Value
Preset Spd 1
#18 (BV18)
Binary Value
Preset Spd 2
#19 (BV19)
Binary Value
Preset Spd 3
#20 (BV20)
Binary Value
Freq Ovrd
#21 (BV21)
Binary Value
Cmd Ovrd
#22 (BV22)
R = Read-only; C = Commandable
Analog Input
Analog Input
Terminal
Object ID
Analog
RR
Input #0
(AI0)
Analog
V/I
Input #1
(AI1)
Analog
RX
Input #2
(AI2)
Analog
AI1*
Input #3
(AI3)
Analog
AI2*
Input #4
(AI4)
* The ETB004Z expansion I/O card is required to use this input.
R = Read-only
https://www.toshiba.com/tic/
®
Table 5. BACnet
Binary Values.(Cont)
Description
Indicates if the drive is ready to run
(ST and Run Command)
Indicates if the drive has reached its
target speed
Commands the drive to start
Commands the rotation direction of the
drive
Commands the drive to reset a fault
Commands the Preset Speed 1 operation
Commands the Preset Speed 2 operation
Commands the Preset Speed 3 operation
Overrides the Frequency Mode 1 (F004)
selection
Overrides the Command Mode (F003)
selection
®
Table 6. BACnet
Analog Inputs.
Object Name
Description
Input level of the RR
RR Level
analog input
Input level of the V/I
V/I Level
analog input
Input level of the RX
RX Level
analog input
Input level of the AI1
AI1 Level
analog input
Input level of the AI2
AI2 Level
analog input
BACnet Setup
Q9 Plus ASD Install/Op Manual
Status
Ready/
Not Ready
Reached/
No
Start/Stop
Rev/Fwd
Reset/No
SP1/None
SP2/None
SP3/None
Enabled/
Off
Enabled/
Off
Value
Percent
(%) of full
scale
Percent
(%) of full
scale
Percent
(%) of full
scale
Percent
(%) of full
scale
Percent
(%) of full
scale
Access
R
R
C
C
C
C
C
C
C
C
Access
R
R
R
R
R
69