AM Output Terminal Function
AM
AM
Program Terminal Analog Output Terminals
This setting determines the output function of the AM analog out-
put terminal. The AM output terminal produces an output voltage
or current that is proportional to the magnitude of the function
assigned to this terminal. Configure the DVM, as shown below, in
accordance with the output signal type of interest (i.e., current or
voltage).
The available assignments for this output terminal are listed in
Table 10 on page
Note: If the monitored item has a positive and a negative
component, use the Expansion I/O Card 2 (P/N ETB004Z).
See the Expansion IO Card Option 2 instruction manual
(P/N 58686) for additional information on the functions of
the option card.
See
F678
To read Voltage at this terminal, configure the meter to read DC
voltage, and connect the leads of the meter to AM (+) and
CCA (-).
To read Current at this terminal, configure the meter to read DC
current, and connect the leads of the meter to AM (+) and
CCA (-).
AM Terminal Setup Parameters
F670
F671
F685
F686
198
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
255.
for additional information on this parameter.
— Set AM Function
— Calibrate AM Terminal
— Output Response Polarity Selection
— Set Zero Level
F670
F671
Direct Access Number —
Parameter Type — Selection List
Factory Default — Output Cur-
rent
Changeable During Run — Yes
https://www.toshiba.com/tic/