Toshiba Q9+ Installation & Operation Manual page 127

Adjustable speed drives
Table of Contents

Advertisement

RX Input Point 1 Rate
Program Torque Setpoints
This parameter is used to set the gain and bias of the RX input
terminal when the RX terminal is used as the control input while
operating in the Torque Control mode.
RX Input Torque Control Setup
Perform the following setup to allow the system to receive Torque
Control input at the RX input terminal:
• Program Fundamental Standard Mode Selection 
Frequency Mode RX.
• Program Fundamental Standard Mode Selection 
Command Mode Selection Terminal Board.
Torque Control
Perform the following setup to allow the system to perform Torque
Control from the RX input terminal:
• Set RX Input Point 1 Rate (F220).
• Set RX Input Point 1 Setting (F216) — the input analog signal
level that corresponds to the torque setting at RX Input Point 1
Rate.
• Set RX Input Point 2 Rate (F221).
• Set RX Input Point 2 Setting (F218) — the input analog signal
level that corresponds to the speed setting at RX Input Point 2
Rate.
• Provide a Run command (F and/or R).
Torque Control is accomplished by establishing an associated V/f
output pattern for a given RX input level.
Once set, as the RX input voltage changes, the ASD output
speed and/or torque will vary in accordance with the above set-
tings.
This parameter sets RX Input Point 1 Rate and is the output
torque value that is associated with the setting of RX Input Point
1 Setting when operating in the Torque Control mode.
This value is entered as -250% to +250% of the rated torque.
https://www.toshiba.com/tic/
F220
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F221
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Torque Settings