RR Input Point 1 Setting
RR
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input
terminal when the RR terminal is used as the control input while
operating in the Speed Control mode or the Torque Control
mode.
This parameter sets the RR input level that is associated with the
RR Input Point 1 Frequency setting when operating in the Speed
control mode or is associated with the RR Input Point 1 Rate set-
ting when operating in the Torque Control mode.
Speed Control
Perform the following setup to allow the system to perform Speed
control from the RR input terminal:
• Set RR Input Point 1 Frequency (F211).
• Set RR Input Point 1 Setting (F210) — the input analog signal
level that corresponds to the frequency setting at RR Input
Point 1 Frequency.
• Set RR Input Point 2 Frequency (F213).
• Set RR Input Point 2 Setting (F212) — the input analog signal
level that corresponds to the frequency setting at RR Input
Point 2 Frequency.
RR Input Speed Control Setup
Perform the following setup to allow the system to receive Speed
control input at the RR input terminal:
• Program Fundamental Standard Mode Selection 
Frequency Mode 1 RR.
• Program Fundamental Standard Mode Selection 
Command Mode Selection Terminal Board.
• Provide a Run command (F and/or R).
Once set, as the RR input voltage changes, the output fre-
quency of the ASD will vary in accordance with the above set-
tings.
This parameter value is entered as 0% to 100% of the RR input
signal range.
https://www.toshiba.com/tic/
F210
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F211
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Frequency Settings
F210
109