Toshiba Q9+ Installation & Operation Manual page 164

Adjustable speed drives
Table of Contents

Advertisement

Virtual Linear Pump Start/Stop Mode
Program Virtual Linear Pump Start and Stop Points
During a properly configured Virtual Linear Pump operation, this
parameter Enables/Disables the ability of the system to receive
transducer input to manage system starts and stops as it per-
tains to the process variable.
This parameter is also used to select the ASD response (Stop or
Start) upon meeting the criteria of
On Forward = Run ASD while measured signal is 
and stop ASD upon reaching
On Reverse = Run ASD while measured signal is 
and stop ASD upon reaching
Settings:
0 — Off
1 — On (Forward Acting)
2 — On (Reverse Acting)
WARNING
The Auto Start-Stop operating mode may result in the unex-
pected Start or Stop of the motor. Signs to this effect are to be
posted at the location of the motor/pump.
Virtual Linear Pump Start-Stop Delay Timer
Program Virtual Linear Pump Start and Stop Points
During a properly configured Virtual Linear Pump operation, this
parameter establishes the time that the Start-Stop criteria of
F388
and
F389
must be maintained to activate the Auto Start-
Stop function.
This feature is used to minimize system responses to rapid fluctu-
ations in the feedback signal.
See
F385
for additional information on this parameter.
152
F385
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F388
and
F389
settings.
F388
F389
setting.
F389
F388
setting.
F388
Direct Access Number —
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — Yes
setting
setting
Direct Access Number —
Parameter Type — Numerical
Factory Default — 5.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6553.5
Units — Seconds
https://www.toshiba.com/tic/
F385
F387

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dn-68249-003

Table of Contents