RR Input Point 1 Rate
Program Torque Setpoints
This parameter is used to set the gain and bias of the RR input
terminal when the RR terminal is used as the control input while
operating in the Torque Control mode.
RR Input Torque Control Setup
Perform the following setup to allow the system to receive Torque
Control input at the RR input terminal:
• Program Fundamental Standard Mode Selection
Frequency Mode RR.
• Program Fundamental Standard Mode Selection
Command Mode Selection Terminal Board.
Torque Control
Perform the following setup to allow the system to perform Torque
Control from the RR input terminal:
• Set RR Input Point 1 Rate (F214).
• Set RR Input Point 1 Setting (F210) — the input analog signal
level that corresponds to the torque setting at RR Input Point 1
Rate.
• Set RR Input Point 2 Rate (F215).
• Set RR Input Point 2 Setting (F212) — the input analog signal
level that corresponds to the frequency setting at RR Input
Point 2 Rate.
• Provide a Run command (F and/or R).
Torque Control is accomplished by establishing an associated V/f
output pattern for a given RR input level.
Once set, as the RR input voltage changes, the output torque of
the ASD will vary in accordance with the above settings.
This parameter sets RR Input Point 1 Rate and is the output
torque value that is associated with the setting of RR Input Point
1 Setting when operating in the Torque Control mode.
This value is entered as 0% to 250% of the rated torque.
https://www.toshiba.com/tic/
–
F214
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F215
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Torque Settings
F214
111