FM Output Terminal Adjustment
Program Terminal Analog Output Terminals
This parameter is used to calibrate the FM analog output.
To calibrate the FM analog output, connect a meter (current or
voltage) as described at F005.
With the ASD running at a known value (e.g., output frequency),
adjust this parameter until the assigned function produces the
desired DC level output at the FM output terminal.
See
F005
for additional information on this parameter.
Type Reset
Program Utilities Type Reset
This feature assists the user when performing fault analysis or by
allowing a quick system setup change when required. Perform-
ing a Type Reset results in one of the following user-selected
post-Reset configurations.
Settings:
0 — None
1 — 50 Hz Setting
2 — 60 Hz Setting
3 — Reset to Factory Settings
4 — Clear Past Trips
5 — Clear Run Timer
6 — Initialize Typeform
7 — *Save User Settings
8 — Restore User Settings
9 — Clear Cumulative Fan Timer
10 — ACC/DEC Unit 0.01s (FA09=0)
11 — ACC/DEC Unit 0.1s (FA09=1)
12 — Set EOI Memory to Default
Note: Selection 12 clears the following user settings: Contrast,
Main Monitor Items, Prohibited Items, and Save User
Settings Information.
Note: Selection 12 does not clear Password and Lockout
Information.
Note: User settings that are stored in the memory of the EOI are
not saved via the Save User Settings selection. The
unsaved functions include the EOI Option Setups, (Utilities
Display Parameters, and (Monitor Setup ) Scrolling
Monitor Select.
76
–
F006
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F008
Direct Access Number —
Parameter Type — Numerical
Factory Default — 236
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number —
Parameter Type — Selection List
Factory Default — None
Changeable During Run — No
https://www.toshiba.com/tic/
F006
F007