Input Function Target 3
Program My Function My Function Unit 3
This parameter plays a role in the setup of the My Function fea-
ture by selecting the functionality of the programmable Input
Function Target 3 terminal.
This setting assigns the function of the programmable Input
Function Target 3 terminal to any one of the user-selectable func-
tions listed in
Table 11 on pg.
14 on pg.
260.
See
F977
for additional information on this parameter.
Output Function Assigned
Program My Function My Function Unit 3
This parameter plays a role in the setup of the My Function fea-
ture by selecting the functionality of the Output Function
Assigned terminal.
This setting assigns the function of the programmable Output
Function Assigned data location to one of the functions listed in
the Input Setting field of
Settings:
0 – 3099
See the My Function Instruction Manual (P/N E6581335) and
F977
for additional information on this parameter.
My Function Percent Data 1
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the
analog signal of the My Function Percent Data 1.
The analog signal is selected using the Input Setting number
from
Table 12 on page
257.
Once the assigned output value reaches the threshold setting of
this parameter the output value is transferred to My Function Out
1.
See the My Function Instruction Manual (P/N E6581335) and
F977
for additional information on this parameter.
My Function Percent Data 2
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the
analog signal of the My Function Percent Data 2.
The analog signal is selected using the Input Setting number
from
Table 12 on page
257.
232
F916
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
256,
Table 12 on pg.
257, or
Table 12 on pg.
257.
F920
Direct Access Number —
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — No
Table
Direct Access Number —
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — No
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.00
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.00
Units — %
https://www.toshiba.com/tic/
F916
F917
F918
F919