Toshiba Q9+ Installation & Operation Manual page 294

Adjustable speed drives
Table of Contents

Advertisement

Cable/Terminal Specifications
Q9 Plus ASD Install/Op Manual
Cable/Terminal
Specifications
Installation should conform to NEC Article 110
(Requirements for Electrical Installations), all
regulations of the Occupational Safety and Health
Administration, and any other applicable national,
regional, or industry codes and standards.
The following ratings are guidelines and shall not
be the sole determining factor of the lug or wire size
used with the Q9 Plus ASD. Application-specific
Table 24. 230-Volt Q9 Plus ASD Cable/Terminal/Torque Specifications.
Wire/Cable Size
Model
Number
VT130Q9+
Input/Output Power
Recommended
2015
14
2025
14
2035
14
2055
10
2080
8
2110
8
2160
6
2220
4
2270
3
2330
2
2400
1/0
2500
1/0
2600
3/0
2750
*3/0
210K
*3/0
212K
*3/0
2750RD
*3/0
210KRD
*3/0
212KRD
*3/0
Note: (*) Indicates that the item is one of a set of two (listed type) parallel cables.
RD Suffix = DCL Included.
282
applicables, wire insulation type, conductor
material, and local and regional regulations are but
a few of the considerations when selecting the
actual lug and wire type to be used with the Q9 Plus
ASD.
Note:
Note:
Lug Size Range
AWG or kcmil
Wire-Size/Lug-
Capacity for
Input/Output Power
Maximum
3Ø-Input
3Ø-Output
10
10
14 to 10
10
10
8
12 to 8
8
10 to 4
3
8 to 2
3
3
4 to 1/0
2
4/0
2 to 300
4/0
6 to 250
2 to 300
4/0
*4/0
*4/0
*4/0
6 to 250
*4/0
*4/0
*4/0
Cable/Terminal specifications are
based on the rated current of the Q9
Plus ASD and Do Not include the 10%
Service Factor.
Use only 75° C copper wire/cable for
motor and power connections.
Terminal
Board Wire
Size
In-Lbs./N·m
TB1 – 4
3Ø-Input 3Ø-Output
Terminals
20
(3-core shield)
Torque to 5.3/
0.6
275/31
https://www.toshiba.com/tic/
Torque
12.4/1.4
26.6/3
47.8/5.4
212/24
360/41
168/19
275/31