Adjustable speed drives
Table of Contents

Advertisement

IP Card Data 3
Program Communications Ethernet Settings
This parameter operates in conjunction with parameter F577.
This parameter is used to configure the IP Data Card 3 section of
the IP address of the device.
See
F577
for additional information on this parameter.
IP Card Data 4
Program Communications  Ethernet Settings
This parameter operates in conjunction with parameter F577.
This parameter is used to configure the IP Data Card 4 section of
the IP address of the device.
See
F577
for additional information on this parameter.
Subnet Mask Data 1
Program Communications Ethernet Settings
This parameter is used to configure the Subnet Mask Data 1 sec-
tion of the subnet mask for the device.
Selecting Manual at parameter
F577
F580
and parameters
create the IP address and Subnet Mask Data, respectively, for
the device.
Subnet Mask Data
Subnet Mask Data
1
2
Subnet Mask Data 2
Program Communications Ethernet Settings
This parameter operates in conjunction with parameter F581.
This parameter is used to configure the Subnet Data Mask 2 sec-
tion of the subnet mask for the device.
See
F581
for additional information on this parameter.
Subnet Mask Data 3
Program Communications Ethernet Settings
This parameter operates in conjunction with parameter F581.
This parameter is used to configure the Subnet Data Mask 3 sec-
tion of the subnet mask for the device.
See
F581
for additional information on this parameter.
https://www.toshiba.com/tic/
F579
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F576
will require that parameters
F582
F584
be used to manually
Subnet Mask Data
Subnet Mask Data
3
F584
Direct Access Number —
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 255
Direct Access Number —
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 255
Direct Access Number —
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 255
4
Direct Access Number —
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 255
Direct Access Number —
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 255
F579
F580
F581
F582
F583
179